LA Fitness Calgary Trail NW - Swimming Pool

4223 Calgary Trail NW Edmonton AB T6J 6Y8 · Aquatic Facility

10 inspections

  1. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • A new circulation pump has been installed that has a larger HP motor. The anti-entrapment compliance plan must be updated and confirmed to still be in compliance as the larger pump can produce higher flow than the previous one. Operations manager confirmed they have hired the pool service provider to complete the report. Ensure a copy is provided as soon as possible to confirm compliance.
  2. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The chemical feed pumps were not connected to the controller through the conduit and dedicated outlets installed as part of the original pool system. A number of extension cords and a y adapter extension cord were used and plugged into outlets. Consolidate the electrical system to utilize the as designed electrical outlets for the chemical system. If these outlets are not in good repair than hire a certified electrician to conduct repairs so the system is working as designed.Operations manager noted that the flow switch requires replacement and their pool service provider was contacted to service the system.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate for the pool was noted at 192 GPM. The pressures on the filters were 25/28PSI respectfully. Check if filters require backwashing as pool service company that installed the new pump confirmed the system was able to achieve >200 GPM. Ensure that the pool flow is maintained at no less than 200 GPM and no more that 211 GPM.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • A new circulation pump has been installed that has a larger HP motor. The anti-entrapment compliance plan must be updated and confirmed to still be in compliance as the larger pump can produce higher flow than the previous one. Operations manager confirmed they have hired the pool service provider to complete the report. Ensure a copy is provided as soon as possible to confirm compliance.
  3. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the system was observed to be 181 GPM. The turnover period based on this flow rate is 4.4 hours. Determine cause of the drop-in flow rate and ensure the system can be brought back to at least 200 GPM as was noted during the last onsite inspection in July 2025.
  4. Risk Management Inspection

    0 infractions

  5. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Due to continuous feeding of the pH chemical pump the pH was observed at 6.4. Make the necessary adjustments to ensure the pH is between 6.8-7.6
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH chemical feed pump was plugged into an outlet with constant electricity. pH on the controller was observed to be 6.4. The pH chemical feed plug was moved to the outlet labeled as pH feed outlet that is connected to the controller. Ensure that the pH chemical feed pump is controlled by the chemical controller and is not left to feed unmonitored. Contact your pool service provider to make the necessary adjustments to bring the pH to within 6.8-7.6
  6. Demand Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of 130 GPM was noted on the Flowvis flow meter. The turnover for the pool is 6.15 hours and exceeds the required 4 hr. turnover. Address the flow rate immediately to ensure proper return of filtered and treated water. Provide the undersigned with a corrective action plan to address the lack of flowrate.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • As the pump was turned off there was no water in the flow cell for the controller probes. Make sure if the probes do not remain dry for extended periods of time as this may cause premature failure.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The pump was turned off by the facility and was closed to patrons. The water was beginning to become cloudy. Ensure that the water chemistry and clarity is corrected before the pool can be reopened.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The underside of the skimmer pots has a build up of biofilm and scum. Clean the lids to prevent contamination of the pool.
  7. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of 130 GPM was noted on the Flowvis flow meter. The turnover for the pool is 6.15 hours and exceeds the required 4 hr. turnover. Address the flow rate immediately to ensure proper return of filtered and treated water. Provide the undersigned with a corrective action plan to address the lack of flowrate.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The underside of the skimmer pots has a build up of biofilm and scum. Clean the lids to prevent contamination of the pool.
  8. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the system was 180 GPM. The turnover period of the pool is longer than 4 hours. Make the necessary adjustments or changes to ensure the pool can maintain the flow at a minimum of 200 GPM. Flow rate issues were noted after a new heater was installed in January.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Significant debris was noted in the NE corner and adjacent to the stairs along the bottom of the basin. Vacuum and remove the debris.
  9. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • 1. There were two damaged section of deck coping/nosing on the edge of the south side of the pool. Tape has been put over the damaged sections as they are sharp edges. Repair/replace the nosing edge.2. Upon further inspection the color in the basin appears to be paint transfer from the platforms used by the swim school onsite. Pitting of the basin finish was also noted. Debris was still noted around the lower part of the stairs. Clean and remove the debris in the basin. Pool service company is scheduled to vacuum the pool on Friday.
  10. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Some colored debris was in the basin that was bleeding onto the pool basin. Debris was also noted around the lower part of the stairs. Clean and remove the debris in the basin.