O'Neil Tower - Swimming Pool
700 9 Street SW Calgary AB T2P 2B5 · Aquatic Facility
9 inspections
- Demand Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH of the water was tested to be 7.80, 7.69, and 7.63. The pH must be kept between 6.8-7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated test results for the chlorine (0.86mg/L) and the pH (7.39) were not consistent with the manual test results for the chlorine (9.46 ppm) and the pH (7.63-7.8). Please calibrate the probes and ensure that the automated test results are consistent with the manual test results.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- There was no Certificate of Compliance for the main drain covers. Please ensure to provide proof of compliance for the main drain cover and depict the correct information onto the AHS-Anti-Entrapment Compliance Plan form. Please visit the following links:- Information: https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-info-complete-anti-entrapment-compliance-form.pdf- Form: https://www.albertahealthservices.ca/frm-21243.pdfOnce the form is filled out and completed, please submit to AHS-EPH/Inspector.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate calculated at 19.1 gpm/sqft. Manufacturer's instructions for TR-140 filter says maximum 15 gpm/sqft. Lower flow rate through both filters (max combined flow is 212 gpm).**OUTSTANDING (2024-07-26). Filtration rate calculated at 17.7 gpm/sqft. Continue to reduce flow, maintain between 202 and 212 gpm.**OUTSTANDING (2025-07-17). The flow meter was not functional during the inspection, so the filtration rate cannot be determined during the inspection. Please fix the flow meter and ensure that it does not exceed the maximum filtration rate for the filters as per the manufacturer's instructions of 15 GPM/square feet.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated test results for the chlorine (3.01 ppm) and the pH (6.09) were not consistent with the manual test results for the chlorine (4.19 ppm) and the pH (7.38). Please calibrate the probes and ensure that the automated test results are consistent with the manual test results.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- There was no Certificate of Compliance for the main drain covers. Please ensure to provide proof of compliance for the main drain cover and depict the correct information onto the AHS-Anti-Entrapment Compliance Plan form. Please visit the following links:- Information: https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-info-complete-anti-entrapment-compliance-form.pdf- Form: https://www.albertahealthservices.ca/frm-21243.pdfOnce the form is filled out and completed, please submit to AHS-EPH/Inspector.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (25ES-214E00008) collected on August 1st, 2025, was rejected by the lab as the sample was received in a weekend/holiday without prior approval (received on August 2nd, 2025).Please submit a new water sample for the swimming pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate calculated at 19.1 gpm/sqft. Manufacturer's instructions for TR-140 filter says maximum 15 gpm/sqft. Lower flow rate through both filters (max combined flow is 212 gpm).**OUTSTANDING (2024-07-26). Filtration rate calculated at 17.7 gpm/sqft. Continue to reduce flow, maintain between 202 and 212 gpm.**OUTSTANDING (2025-07-17). The flow meter was not functional during the inspection, so the filtration rate cannot be determined during the inspection. Please fix the flow meter and ensure that it does not exceed the maximum filtration rate for the filters as per the manufacturer's instructions of 15 GPM/square feet.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated test results for the chlorine (3.01 ppm) and the pH (6.09) were not consistent with the manual test results for the chlorine (4.19 ppm) and the pH (7.38). Please calibrate the probes and ensure that the automated test results are consistent with the manual test results.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- There was no Certificate of Compliance for the main drain covers. Please ensure to provide proof of compliance for the main drain cover and depict the correct information onto the AHS-Anti-Entrapment Compliance Plan form. Please visit the following links:- Information: https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-info-complete-anti-entrapment-compliance-form.pdf- Form: https://www.albertahealthservices.ca/frm-21243.pdfOnce the form is filled out and completed, please submit to AHS-EPH/Inspector.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated test results for the chlorine (3.01 ppm) and the pH (6.09) were not consistent with the manual test results for the chlorine (4.19 ppm) and the pH (7.38). Please calibrate the probes and ensure that the automated test results are consistent with the manual test results.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate calculated at 19.1 gpm/sqft. Manufacturer's instructions for TR-140 filter says maximum 15 gpm/sqft. Lower flow rate through both filters (max combined flow is 212 gpm).**OUTSTANDING (2024-07-26). Filtration rate calculated at 17.7 gpm/sqft. Continue to reduce flow, maintain between 202 and 212 gpm.**OUTSTANDING (2025-07-17). The flow meter was not functional during the inspection, so the filtration rate cannot be determined during the inspection. Please fix the flow meter and ensure that it does not exceed the maximum filtration rate for the filters as per the manufacturer's instructions of 15 GPM/square feet.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- There was no Certificate of Compliance for the main drain covers. Please ensure to provide proof of compliance for the main drain cover and depict the correct information onto the AHS-Anti-Entrapment Compliance Plan form. Please visit the following links:- Information: https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-info-complete-anti-entrapment-compliance-form.pdf- Form: https://www.albertahealthservices.ca/frm-21243.pdfOnce the form is filled out and completed, please submit to AHS-EPH/Inspector.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- UpdatedFiltration rate calculated at 17.7 gpm/sqft. Continue to reduce flow, maintain between 202 and 212 gpm.----------1) Filtration rate calculated at 19.1 gpm/sqft. Manufacturer's instructions for TR-140 filter says maximum 15 gpm/sqft.-Lower flow rate through both filters (max combined flow is 212 gpm)
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Moderate amount of debris in the basin.-Fully clean the basin
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) Filtration rate calculated at 19.1 gpm/sqft. Manufacturer's instructions for TR-140 filter says maximum 15 gpm/sqft.-Lower flow rate through both filters (max combined flow is 212 gpm)2) No observable skimming action from weirs.-Ensure that skimmers are taking in the top layer of water to remove the majority of contaminants
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Moderate amount of debris in the basin.-Fully clean the basin
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) Turnover calculated at 30 hours. This is unlikely to be accurate. 3 different pool volumes on file, this calculation was done with operator's most recent 'confirmation'.-Confirm the pool volume. Turnover requirement is a maximum of 8 hours for a pool constructed before 2006, if water quality can be maintained
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **In progress**VIOLATION: 1. Written policies and plan have been developed, but some sections are incomplete. COMPLETE THE FOLLOWING: 1. Refer to Part 4 of the Pool Standards for the information required in the written policies and plans.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine measured at 0.05 ppm.-Chlorine must be at least 2 ppm in a pool >30C (or 1 ppm in a pool <30C)
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) Turnover calculated at 30 hours. This is unlikely to be accurate. 3 different pool volumes on file, this calculation was done with operator's most recent 'confirmation'.-Confirm the pool volume. Turnover requirement is a maximum of 8 hours for a pool constructed before 2006, if water quality can be maintained2) Automated reader had vastly different results from manual tests - manual pH from inspector was 7.12, reader said 8.4-Repair the automated reader
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- There was lots of debris at the bottom of the pool.-Ensure debris from the pool is removed before operating each day
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **In progress**VIOLATION: 1. Written policies and plan have been developed, but some sections are incomplete. COMPLETE THE FOLLOWING: 1. Refer to Part 4 of the Pool Standards for the information required in the written policies and plans.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- VIOLATION: 1. The basin of the pool is stained a rust-like colour in several areas. COMPLETE THE FOLLOWING: 1. Determine the cause for the staining. Clean and/or repair the basin.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- VIOLATION: 1. Main drain checks are not completed on weekends.COMPLETE THE FOLLOWING: 1. The drain covers must be inspected prior to opening the pool for the day. The results must be recorded in the log.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- VIOLATION: 1. Written policies and plan have been developed, but some sections are incomplete. COMPLETE THE FOLLOWING: 1. Refer to Part 4 of the Pool Standards for the information required in the written policies and plans.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?