Origin at Spring Creek - Swimming Pool

808 Spring Creek Drive Canmore AB T1W 0C5 · Aquatic Facility

14 inspections

  1. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual FAC test measured 6.57ppm while the automatic controller read 3ppm. This is a significant difference. -Ensure the automatic controller reading are consistent with those measured with pool testing kit. Operators pool testing kit has some expired chemicals. Obtain new chemicals for testing and ensure chlorine readings on controller and from testing kit are consistent.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a chip in the bottom of the pool. Please repair.
  2. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on December 22, 2025 was not tested as there was no time of collection on the requisition form. New sample to be submitted.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual FAC test measured 6.57ppm while the automatic controller read 3ppm. This is a significant difference. -Ensure the automatic controller reading are consistent with those measured with pool testing kit. Operators pool testing kit has some expired chemicals. Obtain new chemicals for testing and ensure chlorine readings on controller and from testing kit are consistent.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a chip in the bottom of the pool. Please repair.
  3. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on November 18, 2025 was not tested as there was no id# sticker on the bottle. New sample to be submitted this week.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual FAC test measured 6.57ppm while the automatic controller read 3ppm. This is a significant difference. -Ensure the automatic controller reading are consistent with those measured with pool testing kit. Operators pool testing kit has some expired chemicals. Obtain new chemicals for testing and ensure chlorine readings on controller and from testing kit are consistent.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a chip in the bottom of the pool. Please repair.
  4. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual FAC test measured 6.57ppm while the automatic controller read 3ppm. This is a significant difference. -Ensure the automatic controller reading are consistent with those measured with pool testing kit. Operators pool testing kit has some expired chemicals. Obtain new chemicals for testing and ensure chlorine readings on controller and from testing kit are consistent.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a chip in the bottom of the pool. Please repair.
  5. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual FAC test measured 5.47ppm while the automatic controller read 2.9ppm. This is a significant difference. Operator mentioned Ecolab coming in for automatic controller gel check.-Ensure the automatic controller is functioning accurately at all times.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • November 25, 2024 water sample was not tested as there was no time of collection on the requisition form. Please resample on November 28, 2024.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Written plans could not be located. Find written plans and send for review. If not found, will need to be redone.
  7. Monitoring Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Written plans could not be located. Find written plans and send for review. If not found, will need to be redone.
  8. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Written plans could not be located. Find written plans and send for review. If not found, will need to be redone.
  9. Risk Management Inspection

    3 infractions

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Two of the screws on one of the main drains appear rusty. Please confirm the screws are still in good condition.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Free chlorine level is being checked daily but not recorded. Need to record free chlorine testing results.Combined chlorine level is not being checked. To be checked and recorded daily. As test kit provides a total chlorine result please subtract your free chlorine reading from your total chlorine reading to get your combined chlorine level.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Written plans could not be located. Find written plans and send for review. If not found, will need to be redone.
  10. Risk Management Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Are not checking off on the requisition form for the water samples that the pool water is above 30C when submitting water samples. Need to indicate the pool is being kept above 30C so that water sample is tested for Pseudomonas.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Two of the screws on one of the main drains appear rusty. Please confirm the screws are still in good condition.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Free chlorine level is being checked daily but not recorded. Need to record free chlorine testing results.Combined chlorine level is not being checked. To be checked and recorded daily. As test kit provides a total chlorine result please subtract your free chlorine reading from your total chlorine reading to get your combined chlorine level.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Written plans could not be located. Find written plans and send for review. If not found, will need to be redone.
  11. Monitoring Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Are not checking off on the requisition form for the water samples that the pool water is above 30C when submitting water samples. Need to indicate the pool is being kept above 30C so that water sample is tested for Pseudomonas.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Two of the screws on one of the main drains appear rusty. Please confirm the screws are still in good condition.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Free chlorine level is being checked daily but not recorded. Need to record free chlorine testing results.Combined chlorine level is not being checked. To be checked and recorded daily. As test kit provides a total chlorine result please subtract your free chlorine reading from your total chlorine reading to get your combined chlorine level.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Written plans could not be located. Find written plans and send for review. If not found, will need to be redone.
  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample taken on January 8, 2024 had total coliforms present.-Resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured as 26ppm.
  13. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken this week has the wrong date on it; was taken Nov. 23, but Nov, 22/23 was written on the requisition form so lab did not process it (was received over 24hrs after collection). Resample to be taken.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured as 26ppm.
  14. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample that was received on August 29, 2023, was not tested as the date of collection was not provided on the bottle.-Resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was measured as 26ppm.