Radisson Hotel Calgary Airport - Swimming Pool
6620 36 Street NE Calgary AB T2J 4C8 · Aquatic Facility
31 inspections
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-056E00518) collected on July 02, 2026, was not processed as there was no identification number on the bottle.Please resample the swimming pool as soon as possible.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-121E00088) collected on April 30, 2026, came back unsatisfactory. HPC was elevated (430 CFU/ml). The maximum acceptable concentration for the HPC is 100CFU/mL.Please resample the swimming pool.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-058E00024) collected on February 26, 2026, came back unsatisfactory. HPC was elevated (410 CFU/ml). The maximum acceptable concentration for the HPC is 100CFU/mL.Please resample the swimming pool.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 26ES002E00045Sample collection date was Jan 2, 2026- HPC 470CFU/mL- Resampling advised
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00191Sample collection date was Nov 28, 2025- HPC 170CFU/mL- Resampling advised
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES-275E00791HPC 150 CFU/100mLResampling advised
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00172Sample collection date was Oct 8, 2025- Water sample submitted was received more than 24 hours of collection.- Resampling advised.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 26, 2025, was not tested because the time of collection was not indicated on the requisition form.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES-275E00791HPC 150 CFU/100mLResampling advised
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00172Sample collection date was Oct 8, 2025- Water sample submitted was received more than 24 hours of collection.- Resampling advised.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES-275E00791HPC 150 CFU/100mLResampling advised
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- UNSATISFACTORY WATER SAMPLE TEST RESULTS:1. The water sample collected on August 1, 2025, was unsatisfactory with an HPC of 300 CFU/mL.2. The water sample collected on August 8, 2025, was unsatisfactory with an HPC of 610 CFU/mL.Actions Required:1. Treat the pool water by doing the following:- Increase Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.- Run the water through the circulation system for at least one turnover. - Balance the water, then send another sample for reassessment.Note: The pool must be closed during the treatment and can re-open once the treatment is complete and the pool water is re-balanced to normal parameters. The re-sample test result will be re-assessed by a public health inspector.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on August 1, 2025, was unsatisfactory with an HPC of 300 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.**OUTSTANDING (2025-07-25). The combined chlorine was measured at 1.07 ppm. Please continue to decrease the combined chlorine concentration in the swimming pool water to not exceed 1.0 ppm and ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.**OUTSTANDING (2025-07-25). The flow rate was measured at 115 GPM. Please decrease the flow rate so it does not exceed 106 GPM.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm, and a light chlorine smell was noted at the pool deck. This, inspection, the combined chlorines were measured to be 2.95 ppm, and a notable chlorine smell was noted at the pool deck. Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.**OUTSTANDING (2025-07-23). The combined chlorine cannot be measured during the inspection as the FAC concentration was above 6.0 ppm. Please decrease the FAC concentration to below 6.0 ppm and the combined chlorine concentration to the lowest level possible.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was measured at 54 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration. Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.**Ongoing Violation****OUTSTANDING (2025-07-23). The flow meter was not working during the inspection. Please ensure to fix the flow meter so that the flow is measurable at all times.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- The operator does not have a pool thermometer or probe thermometer to verify the temperature of the swimming pool. This has impacted the ability to verify the temperature of the swimming pool (and may cause improper water sampling and water chemistry). Obtain a thermometer which can verify the temperature of the pool water.**Ongoing Violation****OUTSTANDING (2025-07-23). A thermometer was not available on site. Please obtain a thermometer.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Ongoing Concern** According to pool records (based on the thermostat), The water temperature over the last couple weeks has exceeded 30C in the pool, however, the water samples did not have the >30C box checked off and Pseudomonas was not being tested for.REQUIREMENT: Ensure that the requisition paperwork is properly completed (i.e. select either <30C or >30C depending on the water temperature)
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm and a light chlorine smell was noted at the pool deck.This, inspection, the combined chlorines were measured to be 2.95 ppm and a notable chlorine smell was noted at the pool deck.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration.REQUIREMENT: Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- **Ongoing Violation** 1) The operator does not have a pool thermometer or probe thermometer to verify the temperature of the swimming pool. This has impacted the ability to verify the temperature of the swimming pool (and may cause improper water sampling and water chemistry).REQUIREMENT: Obtain a thermometer which can verify the temperature of the pool water.**Ongoing Violation** 2) The Taylor Test comparator cylinder was heavily stained which will impact how the test results could be interpreted.REQUIREMENT: Obtain a new Taylor Test comparator cylinder.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Ongoing Concern** According to pool records (based on the thermostat), The water temperature over the last couple weeks has exceeded 30C in the pool, however, the water samples did not have the >30C box checked off and Pseudomonas was not being tested for.REQUIREMENT: Ensure that the requisition paperwork is properly completed (i.e. select either <30C or >30C depending on the water temperature)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on February 12, 2025, was not tested because the sample was received more than 24 hours after collection. Resubmit another sample immediately.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm and a light chlorine smell was noted at the pool deck.This, inspection, the combined chlorines were measured to be 2.95 ppm and a notable chlorine smell was noted at the pool deck.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration.REQUIREMENT: Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- **Ongoing Violation** 1) The operator does not have a pool thermometer or probe thermometer to verify the temperature of the swimming pool. This has impacted the ability to verify the temperature of the swimming pool (and may cause improper water sampling and water chemistry).REQUIREMENT: Obtain a thermometer which can verify the temperature of the pool water.**Ongoing Violation** 2) The Taylor Test comparator cylinder was heavily stained which will impact how the test results could be interpreted.REQUIREMENT: Obtain a new Taylor Test comparator cylinder.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Ongoing Concern** According to pool records (based on the thermostat), The water temperature over the last couple weeks has exceeded 30C in the pool, however, the water samples did not have the >30C box checked off and Pseudomonas was not being tested for.REQUIREMENT: Ensure that the requisition paperwork is properly completed (i.e. select either <30C or >30C depending on the water temperature)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 14, 2024, had an HPC Count of 170 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm and a light chlorine smell was noted at the pool deck.This, inspection, the combined chlorines were measured to be 2.95 ppm and a notable chlorine smell was noted at the pool deck.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration.REQUIREMENT: Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- **Ongoing Violation** 1) The operator does not have a pool thermometer or probe thermometer to verify the temperature of the swimming pool. This has impacted the ability to verify the temperature of the swimming pool (and may cause improper water sampling and water chemistry).REQUIREMENT: Obtain a thermometer which can verify the temperature of the pool water.**Ongoing Violation** 2) The Taylor Test comparator cylinder was heavily stained which will impact how the test results could be interpreted.REQUIREMENT: Obtain a new Taylor Test comparator cylinder.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **Ongoing Concern** According to pool records (based on the thermostat), The water temperature over the last couple weeks has exceeded 30C in the pool, however, the water samples did not have the >30C box checked off and Pseudomonas was not being tested for.REQUIREMENT: Ensure that the requisition paperwork is properly completed (i.e. select either <30C or >30C depending on the water temperature)
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, the combined chlorines were measured to be 1.73 ppm and a light chlorine smell was noted at the pool deck.This, inspection, the combined chlorines were measured to be 2.95 ppm and a notable chlorine smell was noted at the pool deck.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration.REQUIREMENT: Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- **Ongoing Violation** 1) The operator does not have a pool thermometer or probe thermometer to verify the temperature of the swimming pool. This has impacted the ability to verify the temperature of the swimming pool (and may cause improper water sampling and water chemistry).REQUIREMENT: Obtain a thermometer which can verify the temperature of the pool water.**Ongoing Violation** 2) The Taylor Test comparator cylinder was heavily stained which will impact how the test results could be interpreted.REQUIREMENT: Obtain a new Taylor Test comparator cylinder.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
6 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- According to pool records (based on the thermostat), The water temperature over the last couple weeks has exceeded 30C in the pool, however, the water samples did not have the >30C box checked off and Pseudomonas was not being tested for.REQUIREMENT: Ensure that the requisition paperwork is properly completed (i.e. select either <30C or >30C depending on the water temperature)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on August 01, 2024 had an HPC count of 1540 CFU/mL.The water sample collected on August 08, 2024 had an HPC count of 740 CFU/mL.REQUIREMENT: Please review the water chemistry and begin treatment for the pool. Collect and send a re-sample after you complete necessary treatments and when the water chemistry is balanced. Indicate on the requisition form that the sample is a ‘resample’
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to be 1.03 ppm. Due to the pool being maintained at a temperature >30C, the minimum residual needs to be 2.0 ppm.REQUIREMENT: Increase and maintain the free chlorine level to a minimum of 2.0 if the water temperature is >30C. Alternatively, maintain the pool at a lower temperature and monitor the temperature so it does not exceed 30C.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured to be 1.73 ppm on the inspector's test kit. On the operational records, the operator obtained a 1.0 ppm for the combined chlorines, and a light chlorine smell was noted at the pool deck.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration.REQUIREMENT: Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- 1) The operator does not have a pool thermometer or probe thermometer to verify the temperature of the swimming pool. This has impacted the ability to verify the temperature of the swimming pool (and may cause improper water sampling and water chemistry).REQUIREMENT: Obtain a thermometer which can verify the temperature of the pool water.2) The Taylor Test comparator cylinder was heavily stained which will impact how the test results could be interpreted.REQUIREMENT: Obtain a new Taylor Test comparator cylinder.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
6 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on August 01, 2024 had an HPC count of 1540 CFU/mL.REQUIREMENT: Please review the water chemistry and begin treatment for the pool. Collect and send a re-sample after you complete necessary treatments and when the water chemistry is balanced. Indicate on the requisition form that the sample is a ‘resample’
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- According to pool records (based on the thermostat), The water temperature over the last couple weeks has exceeded 30C in the pool, however, the water samples did not have the >30C box checked off and Pseudomonas was not being tested for.REQUIREMENT: Ensure that the requisition paperwork is properly completed (i.e. select either <30C or >30C depending on the water temperature)
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to be 1.03 ppm. Due to the pool being maintained at a temperature >30C, the minimum residual needs to be 2.0 ppm.REQUIREMENT: Increase and maintain the free chlorine level to a minimum of 2.0 if the water temperature is >30C. Alternatively, maintain the pool at a lower temperature and monitor the temperature so it does not exceed 30C.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured to be 1.73 ppm on the inspector's test kit. On the operational records, the operator obtained a 1.0 ppm for the combined chlorines, and a light chlorine smell was noted at the pool deck.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration.REQUIREMENT: Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- 1) The operator does not have a pool thermometer or probe thermometer to verify the temperature of the swimming pool. This has impacted the ability to verify the temperature of the swimming pool (and may cause improper water sampling and water chemistry).REQUIREMENT: Obtain a thermometer which can verify the temperature of the pool water.2) The Taylor Test comparator cylinder was heavily stained which will impact how the test results could be interpreted.REQUIREMENT: Obtain a new Taylor Test comparator cylinder.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- According to pool records (based on the thermostat), The water temperature over the last couple weeks has exceeded 30C in the pool, however, the water samples did not have the >30C box checked off and Pseudomonas was not being tested for.REQUIREMENT: Ensure that the requisition paperwork is properly completed (i.e. select either <30C or >30C depending on the water temperature)
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to be 1.03 ppm. Due to the pool being maintained at a temperature >30C, the minimum residual needs to be 2.0 ppm.REQUIREMENT: Increase and maintain the free chlorine level to a minimum of 2.0 if the water temperature is >30C. Alternatively, maintain the pool at a lower temperature and monitor the temperature so it does not exceed 30C.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured to be 1.73 ppm on the inspector's test kit. On the operational records, the operator obtained a 1.0 ppm for the combined chlorines, and a light chlorine smell was noted at the pool deck.REQUIREMENT: Maintain the combined chlorines to the lowest level possible. Some suggested methods could include partial drainage or shock chlorination to breakpoint chlorination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow of 130USGPM is too fast for the filter and exceeds the maximum rate of filtration.REQUIREMENT: Maintain the flow so it does not exceed 15 USGPM/sq.ft or 106 USGPM.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- 1) The operator does not have a pool thermometer or probe thermometer to verify the temperature of the swimming pool. This has impacted the ability to verify the temperature of the swimming pool (and may cause improper water sampling and water chemistry).REQUIREMENT: Obtain a thermometer which can verify the temperature of the pool water.2) The Taylor Test comparator cylinder was heavily stained which will impact how the test results could be interpreted.REQUIREMENT: Obtain a new Taylor Test comparator cylinder.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on April 24, 2024, had an HPC count of 3520 CFU/mL detected.REQUIREMENT: Treat the basin water and collect a resample once treatments are completed and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on February 07, 2024, was not processed due to the lab receiving the water sample 24 hours after collection.REQUIREMENT: Collect another sample and ensure the sample is received by the lab less than 24 hours from collection time.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on January 10, 2024, had TC detected in the sample.REQUIREMENT: Review the water chemistry and begin immediate treatment of the water. Review the water sampling technique to ensure that there wasn’t accidental contamination during the collection. Collect and send a re-sample once treatment is complete and the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on 2023-11-09 showed that HPC was enumerated at greater than 57000 CFU/mL.Requirement: Please treat the swimming pool and resample in accordance with AHS unsatisfactory pool water guidelines.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on October 26, 2023 was not processed due to no identification number on the bottle submitted.REQUIREMENT: Submit a water sample for the basin and ensure an identification sticker is attached to the bottle.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on October 11, 2023 was not processed due to no identification number on the bottle submitted.REQUIREMENT: Submit a water sample for the basin and ensure an identification sticker is attached to the bottle.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on August 24, 2023 was not processed due to no identification number on the bottle submitted.REQUIREMENT: Submit a water sample for the basin and ensure an identification sticker is attached to the bottle.