Radisson Hotel Calgary Airport - Whirlpool
6620 36 Street NE Calgary AB T2J 4C8 · Aquatic Facility
30 inspections
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-184E00146) collected on July 2, 2026, was unsatisfactory. HPC was elevated (4,360 CFU/ml). The maximum acceptable concentration for the HPC is 100CFU/mLPlease treat and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-162E00086) collected on June 10, 2026, was unsatisfactory. HPC was elevated (>57,000 CFU/ml). The maximum acceptable concentration for the HPC is 100CFU/mL Please treat the water, chemically balance and submit another water sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-162E00086) collected on June 10, 2026, was unsatisfactory. HPC was elevated (>57,000 CFU/ml). The maximum acceptable concentration for the HPC is 100CFU/mL Please treat the water, chemically balance and submit another water sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- **UNSATISFACTORY WATER SAMPLE TEST RESULT**The water sample collected on March 20, 2026, was unsatisfactory with the presence of Total Coliforms.The water sample collected on March 25, 2026, had a Heterotrophic Plate Count of >57,000 CFU/mL.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- **UNSATISFACTORY WATER SAMPLE TEST RESULT**The water sample collected on March 20, 2026, was unsatisfactory with the presence of Pseudomonas aeruginosa.The water sample collected on March 25, 2026, tested positive for Pseudomonas aeruginosa.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on March 25, 2026, had a Heterotrophic Plate Count of >57,000 CFU/mL.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on March 20, 2026, was unsatisfactory with the presence of Pseudomonas aeruginosa.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00802Sample collection date Oct 02, 2025HPC 210 CFU/mLResampling advised.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00173Sample collection date was Oct 8, 2025- Water sample submitted was received more than 24 hours of collection.- Resampling advised.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 26, 2025, was not tested because the time of collection was not indicated on the requisition form.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 26, 2025, was not tested because the time of collection was not indicated on the requisition form.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00802Sample collection date Oct 02, 2025HPC 210 CFU/mLResampling advised.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00173Sample collection date was Oct 8, 2025- Water sample submitted was received more than 24 hours of collection.- Resampling advised.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00802Sample collection date Oct 02, 2025HPC 210 CFU/mLResampling advised.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00173Sample collection date was Oct 8, 2025- Water sample submitted was received more than 24 hours of collection.- Resampling advised.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ID 25ES275E00802Sample collection date Oct 02, 2025HPC 210 CFU/mLResampling advised.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 30, 2025, was not tested due to the identification number not indicated on the bottle. Please submit another water sample immediately.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on August 1, 2025, was unsatisfactory with an HPC of 300 CFU/mL.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 30, 2025, was not tested due to the identification number not indicated on the bottle. Please submit another water sample immediately.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was measured at 100 GPM, and the filtration rate was measured at 14.16 GPM/feet square, accordingly. The filtration rate must not exceed 12.5 GPM/square feet, and the flow rate must not exceed 88.25 GPM. Please maintain the flow rate between 57.5 GPM and 88.25 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine concentration was measured at 2.70 ppm. The inspector informed the operator to decrease the level of combined chlorine to below 1.0 ppm, or ideally below 0.5 ppm, if possible, to maximize the bather comfort.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The clock by the whirlpool was missing. Please re-equip the whirlpool with a clock.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.If the flow meter is consistently jamming, determine the cause (e.g. replacing a gasket in the sand filter) or replace the meter with a digital gauge.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample that was collected on March 12, 2025 was unsatisfactory. The result showed Pseudomonas aeruginosa being isolated. Thus, ensure to treat the whirlpool and submit another sample. Instructions will be provided via an Information Sheet document. Please ensure to follow the instructions, as required.**CLOSURE ORDER ISSUED (2025-03-20). The water sample that was collected on March 18, 2025 was unsatisfactory. The result showed Pseudomonas aeruginosa being isolated.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample that was collected on March 12, 2025 was unsatisfactory. The result showed a Heterotrophic Plate Count of 11,680 CFU/mL. Please treat the facility, as instructed.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.If the flow meter is consistently jamming, determine the cause (e.g. replacing a gasket in the sand filter) or replace the meter with a digital gauge.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample that was collected on March 12, 2025 was unsatisfactory. The result showed Pseudomonas aeruginosa being isolated. Thus, ensure to treat the whirlpool and submit another sample. Instructions will be provided via an Information Sheet document. Please ensure to follow the instructions, as required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample that was collected on March 12, 2025 was unsatisfactory. The result showed a Heterotrophic Plate Count of 11,680 CFU/mL. Please treat the facility, as instructed.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.If the flow meter is consistently jamming, determine the cause (e.g. replacing a gasket in the sand filter) or replace the meter with a digital gauge.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.If the flow meter is consistently jamming, determine the cause (e.g. replacing a gasket in the sand filter) or replace the meter with a digital gauge.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on February 12, 2025, was not tested because the sample was received more than 24 hours after collection. Another water sample will be submitted.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.If the flow meter is consistently jamming, determine the cause (e.g. replacing a gasket in the sand filter) or replace the meter with a digital gauge.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.If the flow meter is consistently jamming, determine the cause (e.g. replacing a gasket in the sand filter) or replace the meter with a digital gauge.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on October 23, 2024, has Pseudomonas isolated in the sample.REQUIREMENT: Please begin treatment for the hot tub immediately. Submit a re-sample after you complete necessary treatments and the water chemistry is rebalanced. Indicate on the requisition form that the sample is a ‘resample’.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.If the flow meter is consistently jamming, determine the cause (e.g. replacing a gasket in the sand filter) or replace the meter with a digital gauge.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine level was measured to 1.52 ppm.REQUIREMENT: Maintain the free chlorine level at or above 2.0 ppm for a basin kept higher than 30C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Violation** The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.If the flow meter is consistently jamming, determine the cause (e.g. replacing a gasket in the sand filter) or replace the meter with a digital gauge.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on July 17, 2024, had Pseudomonas isolated in the sample.REQUIREMENT: Begin treatment for the whirlpool immediately. Submit a re-sample on Monday after you complete necessary treatments and when the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 17, 2024, had an HPC count of 3200 CFU/mL in the sample.REQUIREMENT: Begin treatment for the whirlpool immediately. Submit a re-sample on Monday after you complete necessary treatments and when the water chemistry is rebalanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- **Ongoing Violation** The basin finishing is heavily degrading. Numerous areas have lost the (presumed) paint finishing.REQUIREMENT: Repair and refinish this basin so that it is easy to clean.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- **Ongoing Violation** The basin finishing is heavily degrading. Numerous areas have lost the (presumed) paint finishing.REQUIREMENT: Repair and refinish this basin so that it is easy to clean.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on February 07, 2024, was not processed due to the lab receiving the water sample 24 hours after collection.REQUIREMENT: Collect another sample and ensure the sample is received by the lab less than 24 hours from collection time.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The basin finishing is heavily degrading. Numerous areas have lost the (presumed) paint finishing.REQUIREMENT: Repair and refinish this basin so that it is easy to clean.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample submitted on submitted on 2023-12-27 showed that Pseudomonas aeruginosa was isolated per 100mL.REQUIREMENT: Please treat the whirlpool in accordance with AHS unsatisfactory pool water sample and resample (please ensure to label as resample).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for the basin appears to be jammed; a reading from the flow meter could not be taken during the inspection.REQUIREMENT: Repair the flow meter and ensure the flow is between the minimum and maximum flow rates as specified.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The basin finishing is heavily degrading. Numerous areas have lost the (presumed) paint finishing.REQUIREMENT: Repair and refinish this basin so that it is easy to clean.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample submitted on submitted on 2023-12-27 showed that Pseudomonas aeruginosa was isolated per 100mL.REQUIREMENT: Please treat the whirlpool in accordance with AHS unsatisfactory pool water sample and resample (please ensure to label as resample).
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample submitted on submitted on 2023-11-09 showed that Pseudomonas aeruginosa was isolated per 100mL.REQUIREMENT: Please treat the whirlpool in accordance with AHS unsatisfactory pool water sample and resample (please ensure to label as resample).
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on submitted on 2023-11-09 showed that HPC was enumerated at 480 CFU/mL.Requirement: Please treat the whirlpool as indicated and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on October 26, 2023, was not processed due to no identification number on the bottle submitted.REQUIREMENT: Submit a water sample for the basin and ensure an identification sticker is attached to the bottle.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on August 24, 2023 was not processed due to no identification number on the bottle submitted.REQUIREMENT: Submit a water sample for the basin and ensure an identification sticker is attached to the bottle.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on August 14, 2023, has pseudomonas isolated in the sample.REQUIREMENT: Begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?