Service Plus Inn & Suites - Whirlpool
10810 107A Avenue Grande Prairie AB T8V 7A9 · Aquatic Facility
23 inspections
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result for sample collected on April 15, 2026:Total Coliforms: Present. Ensure hot tub is drained and cleaned. Balance the water chemistry before submitting another water sample next week.Pseudomonas results are pending.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result for sample collected on April 8, 2026:HPC: 580 cfu per 100 mL.Ensure HPC count is less than 100 cfu per 100 mL.Update: April 17, 2026Results Pending.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result for sample collected on April 8, 2026:HPC: 580 cfu per 100 mL.Ensure HPC count is less than 100 cfu per 100 mL.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result for sample collected on March 24, 2026:Pseudomonas Aeruginosa: IsolatedEnsure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on March 24, 2026 - Unsatisfactory water result received - HC >57000 CFU/ml. Ensure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result for sample collected on March 11, 2026:Pseudomonas Aeruginosa: IsolatedEnsure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received - HC >57000 CFU/ml. Ensure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result for sample collected on January 27, 2026:Pseudomonas Aeruginosa: IsolatedEnsure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result for sample collected on January 27, 2026:Total Coliforms: >57,000 CFU/mL.Ensure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.*** OUTSTANDING: December 04, 2025Ensure that all leaks are repaired and the mechanical room is cleaned thoroughly afterwards.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Leaks were observed in the whirlpool pipes located in the mechanical room. Ensure that all leaks are repaired.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result for sample collected on October 1, 2025:Pseudomonas Aeruginosa: IsolatedEnsure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result for sample collected on October 1, 2025:Total Coliforms: >57,000 CFU/mL.Ensure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result for sample collected on August 20, 2025:Pseudomonas Aeruginosa: IsolatedEnsure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.Update: August 27, 2025Hot tub was closed, and closure sign was posted.Update: September 10, 2025Closure sign was missing. Ensure hot tub remains closed until a satisfactory water result is obtained. Post closure sign again.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result for sample collected on August 20, 2025:Total Coliforms: >57,000 CFU/mL.Ensure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result for sample collected on August 20, 2025:Pseudomonas Aeruginosa: IsolatedEnsure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.Update: August 27, 2025Hot tub was closed, and closure sign was posted.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result for sample collected on August 20, 2025:Total Coliforms: >57,000 CFU/mL.Ensure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Not observed during 13/12/2023 inspectionThe hot tub's emergency shut off is not in good working order.REPAIR / REPLACE EMERGENCY SHUTOFFUpdate: August 27, 2025The emergency shut off switch is still not repaired. Ensure the switch is repaired within 2 weeks.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result for sample collected on August 20, 2025:Pseudomonas Aeruginosa: IsolatedEnsure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result for sample collected on August 20, 2025:Total Coliforms: >57,000 CFU/mL.Ensure hot tub is closed, drained, cleaned and shock chlorinated. Hot tub must remain closed until a satisfactory result is received.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Not observed during 13/12/2023 inspectionThe hot tub's emergency shut off is not in good working order.REPAIR / REPLACE EMERGENCY SHUTOFF
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received, collection date August 13, 2025:Total Coliforms Present.Ensure hot tub is drained, cleaned and resampled next week.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Not observed during 13/12/2023 inspectionThe hot tub's emergency shut off is not in good working order.REPAIR / REPLACE EMERGENCY SHUTOFF
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received, collection date July 9. 2025 - Pseudomonas - Isolated.Ensure to backwash, super chlorinate, run water through circulation 4 to 6 hours, drain, scrub with acid/sanitizer, rinse, refill pool, adjust chemistry and resample.Pseudomonas aeruginosa Information Sheet will be sent via email with the report,
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received - HC >57000 CFU/ml.Superchlorinate the pool.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Not observed during 13/12/2023 inspectionThe hot tub's emergency shut off is not in good working order.REPAIR / REPLACE EMERGENCY SHUTOFF
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date is June 11, 2025 - HPC > 57 000 CFU/ml.Superchlorinate the pool and resample.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Not observed during 13/12/2023 inspectionThe hot tub's emergency shut off is not in good working order.REPAIR / REPLACE EMERGENCY SHUTOFF
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Not observed during 13/12/2023 inspectionThe hot tub's emergency shut off is not in good working order.REPAIR / REPLACE EMERGENCY SHUTOFF
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas aeruginosa was isolated.Ensure hot tub is closed for public use immediately. Drain, clean, refill, shock, rebalance water chemistry before resampling. Hot tub to remain closed until satisfactory water result.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC: 280 cfu/mLEnsure hot tub is closed for public use immediately. Drain, clean, refill, shock, rebalance water chemistry before resampling. Hot tub to remain closed until satisfactory water result.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Not observed during 13/12/2023 inspectionThe hot tub's emergency shut off is not in good working order.REPAIR / REPLACE EMERGENCY SHUTOFF
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Not observed during 13/12/2023 inspectionThe hot tub's emergency shut off is not in good working order.REPAIR / REPLACE EMERGENCY SHUTOFF
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory bacteriological water sample results TC presentIncrease Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.Run the water through the circulation system for at least one turnover. Balance the water, resample as soon as possible.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The hot tub's emergency shut off is not in good working orderREPAIR / REPLACE EMERGENCY SHUTOFF
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?