Shane Homes YMCA at Rocky Ridge - Whirlpool

11300 Rocky Ridge Road NW Calgary AB T3G 5H3 · Aquatic Facility

Inspection summary

Shane Homes YMCA at Rocky Ridge - Whirlpool has been inspected 21 times by Alberta Health Services (Environmental Public Health) since November 23, 2023. The most recent inspection, on September 10, 2026, recorded 1 infraction.

1 of 21 inspections on record found no infractions at all. In the past 12 months there were 6 inspections with 9 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality, Chemicals and toxic substances and Food temperature control.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 28 times across 15 separate inspections, most recently on July 24, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 23 times across 16 separate inspections, most recently on November 17, 2025. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

  • Food temperature controlHigher risk

    Inspectors check that anything that has to be kept at a set temperature, such as chilled or hot food, or equipment like sterilizers, stays in its safe range and that accurate thermometers are on hand. With food, temperature problems are one of the most common causes of food poisoning.

    Recorded 3 times across 3 separate inspections, most recently on September 10, 2026. For example: Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

21 inspections

  1. Demand Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Repeat violation cited on September 10, 2026:Pile of sand was noted at the bottom of the whirlpool basin.The management indicated that the replacement of the filter laterals is currently underway but could not give a definite date when it will be replaced due to shipment issues as the parts are coming from the United States of America.Remove the sand and replace the filter laterals.Previous violation:Sand build-up was noted at the bottom of the pool.
  2. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1. Water sample collected on 23/7/2026, tested positive for Total Coliforms.2. Water sample collected on 23/7/2026, tested positive for Pseudomonas aeruginosaTreat and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 23/7/2026, had a Heterotrophic Plate Count of 520 CFU/mL.Treat and resample.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • 1. The hot tub water temperature was measured above 40°C.Adjust the temperature and ensure the hot tub water measures below 40°C.2. Sand build-up was noted at the bottom of the pool.
  3. Demand Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • 1. The hot tub water temperature was measured above 40°C.Adjust the temperature and ensure the hot tub water measures below 40°C.2. Sand build-up was noted at the bottom of the pool.
  4. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on 06/02/2026 tested positive for Pseudomonas aeruginosa.Treat and resample.
  5. Monitoring Inspection

    0 infractions

  6. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 13/11/2025 was rejected because the sample was received more than 24 hours after collection.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The combine chlorine is 2.54 ppm.2) The total alkalinity is 39.Adjust the water chemistry to measure the combine chlorine as low as possible.Adjust the water chemistry to measure the total alkalinity between 60 mg/L to 180 mg/L
  7. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on 22/08/2025 tested positive for Pseudomonas.Treat and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 22/08/2025 had a HPC of 7600 CFC/mlTreat and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The combine chlorine is 2.54 ppm.2) The total alkalinity is 39.Adjust the water chemistry to measure the combine chlorine as low as possible.Adjust the water chemistry to measure the total alkalinity between 60 mg/L to 180 mg/L
  8. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sampled collected on 01/08/2025, tested positive for Pseudomonas.Treat and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sampled collected on 01/08/2025, had a HPC of 3820 CFC/mL.Treat and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The combine chlorine is 2.54 ppm.2) The total alkalinity is 39.Adjust the water chemistry to measure the combine chlorine as low as possible.Adjust the water chemistry to measure the total alkalinity between 60 mg/L to 180 mg/L
  9. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The combine chlorine is 2.54 ppm.2) The total alkalinity is 39.Adjust the water chemistry to measure the combine chlorine as low as possible.Adjust the water chemistry to measure the total alkalinity between 60 mg/L to 180 mg/L
  10. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Recurring violation:The bacteriological water sample taken on February 18, 2025, had Pseudomonas aeruginosa isolated.Previous violation:Pseudomonas aeruginosa isolated in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Recurring violation:The bacteriological water sample taken on February 18, 2025, had 480 CFU/mL Heterotrophic Plate Count (HPC) Previous violation:HPC at a value of >57,000 CFU/mL detected in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample was rejected as sample was received by the lab more than 24 hours it was collected.Resample the Hot Tub.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The combine chlorine is 2.54 ppm.2) The total alkalinity is 39.Adjust the water chemistry to measure the combine chlorine as low as possible.Adjust the water chemistry to measure the total alkalinity between 60 mg/L to 180 mg/L
  11. Risk Management Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Recurring violation:The bacteriological water sample taken on February 18, 2025, had Pseudomonas aeruginosa isolated.Previous violation:Pseudomonas aeruginosa isolated in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Recurring violation:The bacteriological water sample taken on February 18, 2025, had 480 CFU/mL Heterotrophic Plate Count (HPC) Previous violation:HPC at a value of >57,000 CFU/mL detected in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample was rejected as sample was received by the lab more than 24 hours it was collected.Resample the Hot Tub.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The combine chlorine is 2.54 ppm.2) The total alkalinity is 39.Adjust the water chemistry to measure the combine chlorine as low as possible.Adjust the water chemistry to measure the total alkalinity between 60 mg/L to 180 mg/L
  12. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas aeruginosa isolated in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC at a value of >57,000 CFU/ml detected in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample was rejected as sample was received by the lab more than 24 hours it was collected.Resample the Hot Tub.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The combine chlorine is 2.54 ppm.2) The total alkalinity is 39.Adjust the water chemistry to measure the combine chlorine as low as possible.Adjust the water chemistry to measure the total alkalinity between 60 mg/L to 180 mg/L
  13. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas aeruginosa isolated in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC at a value of >57,000 CFU/ml detected in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample was rejected as sample was received by the lab more than 24 hours it was collected.Resample the Hot Tub.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
  14. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas aeruginosa isolated in water sample collected on February 4, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC at a value of >57,000 CFU/ml detected in water sample collected on February 4, 2025.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
  15. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas aeruginosa detected in water sample collected on Jan 21st 25. - Treat and resample
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC at a value of 57000 CFU/ml detected in water sample collected on Jan 21st 25. - Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
  16. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC at 57000 CFU/ml detected in water sample collected on Dec 24th 2024. - Treat and resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
  17. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
  18. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • WC-24-0015180Sample had TC present. Treat and resample ASAP.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
  19. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Dec 5 Sample not processed, no date and time of collection provided. Dec 12 Sample not processed, no sticker on bottle.Resamle ASAP.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
  20. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample not processed, no date and time of collection provided. Resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.
  21. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine measured 2.41 ppm. Please shock to reduce to <1 ppm.