Village Square Leisure Centre - Dive Pool
2623 56 Street NE Calgary AB T1Y 6E7 · Aquatic Facility
16 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-183E00097) collected on July 01, 2026, was not processed as it was received more than 24 hours after collection.Please resample the swimming pool as soon as possible.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-126E00412) submitted the week of May 4, 2026, was not tested as the date of collection was not listed on the lab requisition form.Please resample the dive pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- April 22, 2026, water sample was unsatisfactory. HPC @ 2880 CFU/ml.Please resample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on March 25, 2026, was unsatisfactory with an HPC of 150 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on August 20, 2025, was unsatisfactory with an HPC of 810 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on July 30, 2025, was unsatisfactory with the presence of Total Coliforms. The spray park must be closed, then to be treated as follows: increase the Free Available Chlorine (FAC) to 10 ppm and maintain a pH of 7.2, then run the water through one turnover of 33.2 minutes, then re-balance the water, and send another sample for bacteriological testing.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample water submitted on January 8, 2025, had Heterotrophic Plate Count enumerated at 180 CFU/mL.-Please submit another water sample and ensure proper sampling procedures are followed to prevent contamination. Label as resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample not processed because the sample was received more than 24 hours after collection.-Please resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration rate was too high, measured at 18.07 GPM/Sqft. The filter rate according to manufacturer's specification is 14.6 GPM/Sqft.-Please lower the filtration rate to meet this specification.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?