Wingate by Wyndham Lethbridge - Pool

120 Stafford Drive S Lethbridge AB T1J 4W4 · Aquatic Facility

30 inspections

  1. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 45 ppm. Please ensure the alkalinity is maintained between 60-180 ppm at all times.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The stairs for the slide require some cleaning. The chip in the railing/edge of the stairs for the slide had been repaired. Please clean the slide stairs.
  2. Risk Management Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The chlorine level was measured to be 0.96 ppm which is slightly lower than the 1.0 ppm that is required. Please bump up the chlorine and ensure that it is kept at or above 1.0 ppm at all times.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 49 ppm. Please ensure the alkalinity is maintained between 60-180 ppm at all times.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The stairs for the slide require some cleaning. The railing/edge of the stairs for the slide had a new chip that had some sharp edges. Please clean the slide stairs and repair the chipped area.
  3. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The chlorine level was measured to be 0.96 ppm which is slightly lower than the 1.0 ppm that is required. Please bump up the chlorine and ensure that it is kept at or above 1.0 ppm at all times.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 49 ppm. Please ensure the alkalinity is maintained between 60-180 ppm at all times.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The stairs for the slide require some cleaning. The railing/edge of the stairs for the slide had a new chip that had some sharp edges. Please clean the slide stairs and repair the chipped area.
  4. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  5. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • An HPC of 1180 CFU/mL was isolated in the sample collected Oct 15.Please address the HPC in the pool and submit a resample once complete.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  6. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 880 CFU/mL in water sample collected August 27.Please address the HPC in the pool and submit a resample once complete.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  8. Risk Management Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 2000 CFU/mL
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  9. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  10. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms present.Sample collected July 16, 2025.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Heterotrophic plate count: 2,300 CFU/mL.Sample collected July 16, 2025.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  11. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  12. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • An HPC of 110 CFU/mL was isolated in the sample collected May 21. Please address the HPC in the pool and submit a resample once complete.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  13. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  14. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • An HPC of 270 CFU/mL was isolated in the sample collected April 23. Please address the HPC in the pool and submit a resample once complete.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  15. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  16. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC of 470 CFU/mL was isolated in the December 2 sample. Please address the HPC in the pool and submit a resample once complete.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  17. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free available chlorine (FAC) was 0.95ppm. Please ensure that FAC is 1ppm and higher.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  18. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Two of the four main drains do not have screws. Please ensure that the two drains are securely attached to the basin floor.
  19. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The frame for the light fixture on the wall of the pool basin is loose. It does not come off the wall completely but does come far enough that fingers or toes could get stuck inside. Operator is aware of this and is looking into a solution. Please securely attach all light fixtures to the pool basin walls.
  20. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • An HPC of 150 CFU/mL was isolated in the September 9 sample. Please address the HPC in the pool and submit a resample once complete
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The frame for the light fixture on the wall of the pool basin is loose. It does not come off the wall completely but does come far enough that fingers or toes could get stuck inside. Operator is aware of this and is looking into a solution. Please securely attach all light fixtures to the pool basin walls.
  21. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The frame for the light fixture on the wall of the pool basin is loose. It does not come off the wall completely but does come far enough that fingers or toes could get stuck inside. Operator is aware of this and is looking into a solution. Please securely attach all light fixtures to the pool basin walls.
  22. Monitoring Inspection

    5 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free available chlorine was noted to be 0.91 ppm. Please ensure that the chlorine level is maintained at 1.0 ppm or higher.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 48 ppm. Please ensure the alkalinity is maintained between 60-180 ppm at all times.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **The flow meter was still not working. The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • *This will all be addressed tomorrow. 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The light fixture on the side of the pool basin was not securely attached to the wall. Please securely attach all light fixtures to the pool basin walls.
  23. Risk Management Inspection

    5 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured at 45 ppm. Please ensure the alkalinity is maintained between 60 - 180 ppm at all times. The combined chlorine in the pool was measured at 1.07 ppm. The continuously high combined chlorine levels were discussed with the pool operator. He will increase the chlorine to shock the pool tonight. For bather comfort, please ensure that the combined chlorine levels are kept as low as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **The flow meter was still not working. The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • There was a significant scum line noted around the edge of the entire pool. Pool operator was made aware of this. Please clean the scum line and keep cleaning it on a regular basis to avoid a significant buildup.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • ** The grate at the top of the slide entrance had been repaired. The other items are still remaining. 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **There had been no change in the record keeping. This was discussed with the pool operator. The records for the pool water testing were not filled out appropriately. The automated controller readings were not being recorded at all. The chlorine levels were recorded but show consistent levels that are below acceptable chlorine ranges (ie. 0.17 ppm in the pool) with no corrective action and no rise in levels during the next test.
  24. Demand Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample result: HPC 260CFU/ml
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured at 45 ppm. Please ensure the alkalinity is maintained between 60 - 180 ppm at all times. The combined chlorine in the pool was measured at 1.07 ppm. The continuously high combined chlorine levels were discussed with the pool operator. He will increase the chlorine to shock the pool tonight. For bather comfort, please ensure that the combined chlorine levels are kept as low as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **The flow meter was still not working. The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • There was a significant scum line noted around the edge of the entire pool. Pool operator was made aware of this. Please clean the scum line and keep cleaning it on a regular basis to avoid a significant buildup.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • ** The grate at the top of the slide entrance had been repaired. The other items are still remaining. 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **There had been no change in the record keeping. This was discussed with the pool operator. The records for the pool water testing were not filled out appropriately. The automated controller readings were not being recorded at all. The chlorine levels were recorded but show consistent levels that are below acceptable chlorine ranges (ie. 0.17 ppm in the pool) with no corrective action and no rise in levels during the next test.
  25. Risk Management Inspection

    5 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured at 45 ppm. Please ensure the alkalinity is maintained between 60 - 180 ppm at all times. The combined chlorine in the pool was measured at 1.07 ppm. The continuously high combined chlorine levels were discussed with the pool operator. He will increase the chlorine to shock the pool tonight. For bather comfort, please ensure that the combined chlorine levels are kept as low as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **The flow meter was still not working. The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • There was a significant scum line noted around the edge of the entire pool. Pool operator was made aware of this. Please clean the scum line and keep cleaning it on a regular basis to avoid a significant buildup.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • ** The grate at the top of the slide entrance had been repaired. The other items are still remaining. 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **There had been no change in the record keeping. This was discussed with the pool operator. The records for the pool water testing were not filled out appropriately. The automated controller readings were not being recorded at all. The chlorine levels were recorded but show consistent levels that are below acceptable chlorine ranges (ie. 0.17 ppm in the pool) with no corrective action and no rise in levels during the next test.
  26. Risk Management Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC is high which is indicative of disinfection not keeping up with demand.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured at 45 ppm. Please ensure the alkalinity is maintained between 60 - 180 ppm at all times. The combined chlorine in the pool was measured at 1.07 ppm. The continuously high combined chlorine levels were discussed with the pool operator. He will increase the chlorine to shock the pool tonight. For bather comfort, please ensure that the combined chlorine levels are kept as low as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **The flow meter was still not working. The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • There was a significant scum line noted around the edge of the entire pool. Pool operator was made aware of this. Please clean the scum line and keep cleaning it on a regular basis to avoid a significant buildup.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • ** The grate at the top of the slide entrance had been repaired. The other items are still remaining. 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **There had been no change in the record keeping. This was discussed with the pool operator. The records for the pool water testing were not filled out appropriately. The automated controller readings were not being recorded at all. The chlorine levels were recorded but show consistent levels that are below acceptable chlorine ranges (ie. 0.17 ppm in the pool) with no corrective action and no rise in levels during the next test.
  27. Risk Management Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC is high which is indicative of disinfection not keeping up with demand.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured at 14 ppm. Please ensure the alkalinity is maintained between 60 - 180 ppm at all times. The combined chlorine in the pool was measured at 1.10 ppm. Please shock the water to bring down the combined chlorine level. For bather comfort, maintain this level below 1.0 ppm
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The water in the pool was quite cloudy. The main drains were barely visible at the time of the inspection. Determine the reason for the water clarity issues and fix ASAP.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The white grate at the top of the slide was missing a piece and had sharp edges.4. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The records for the pool water testing were not filled out appropriately. The automated controller readings were not being recorded at all. The chlorine levels were recorded but show consistent levels that are below acceptable chlorine ranges (ie. 0.17 ppm in the pool) with no corrective action and no rise in levels during the next test.
  28. Risk Management Inspection

    5 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured at 14 ppm. Please ensure the alkalinity is maintained between 60 - 180 ppm at all times. The combined chlorine in the pool was measured at 1.10 ppm. Please shock the water to bring down the combined chlorine level. For bather comfort, maintain this level below 1.0 ppm
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The water in the pool was quite cloudy. The main drains were barely visible at the time of the inspection. Determine the reason for the water clarity issues and fix ASAP.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The white grate at the top of the slide was missing a piece and had sharp edges.4. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The records for the pool water testing were not filled out appropriately. The automated controller readings were not being recorded at all. The chlorine levels were recorded but show consistent levels that are below acceptable chlorine ranges (ie. 0.17 ppm in the pool) with no corrective action and no rise in levels during the next test.
  29. Risk Management Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC is elevated.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured at 14 ppm. Please ensure the alkalinity is maintained between 60 - 180 ppm at all times. The combined chlorine in the pool was measured at 1.10 ppm. Please shock the water to bring down the combined chlorine level. For bather comfort, maintain this level below 1.0 ppm
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The water in the pool was quite cloudy. The main drains were barely visible at the time of the inspection. Determine the reason for the water clarity issues and fix ASAP.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The white grate at the top of the slide was missing a piece and had sharp edges.4. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The records for the pool water testing were not filled out appropriately. The automated controller readings were not being recorded at all. The chlorine levels were recorded but show consistent levels that are below acceptable chlorine ranges (ie. 0.17 ppm in the pool) with no corrective action and no rise in levels during the next test.
  30. Risk Management Inspection

    5 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured at 14 ppm. Please ensure the alkalinity is maintained between 60 - 180 ppm at all times. The combined chlorine in the pool was measured at 1.10 ppm. Please shock the water to bring down the combined chlorine level. For bather comfort, maintain this level below 1.0 ppm
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter did not appear to be working (the bead was stuck in the middle of the tube) at the time of the inspection. Please repair/replace the flow meter.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The water in the pool was quite cloudy. The main drains were barely visible at the time of the inspection. Determine the reason for the water clarity issues and fix ASAP.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • 1. The stairs for the slide had a buildup of dirt and grime on them. 2. There were chips in the stair railing (previous ones where the filling had come out) that are now large with sharp edges. 3. The white grate at the top of the slide was missing a piece and had sharp edges.4. The metal portion of the railing above the slide entrance was severely rusted. Chips of rusted metal were coming off of the railing.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The records for the pool water testing were not filled out appropriately. The automated controller readings were not being recorded at all. The chlorine levels were recorded but show consistent levels that are below acceptable chlorine ranges (ie. 0.17 ppm in the pool) with no corrective action and no rise in levels during the next test.