Kenwood Acad. (H/S)

5015 S Blackstone (1500E), CHICAGO, IL 60615 · School

24 inspections

  1. Canvass Re-Inspection

    5 infractions

    • 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
      • TIMED FAUCET NOT FUNCTIONING PROPERLY AT MIDDLE SINK IN GIRLS WASHROOM 270. WATER MUST RUN CONTINUOUSLY FOR AT LEAST 15 SECONDS BEFORE REACTIVATING FAUCET.
    • 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
      • : OBSERVED LEAKING DRAINPIPE UNDER 3-COMPARTMENT SINK NEAR UNUSED WALK-IN COOLERS, AND UNDER LEFT SINK IN BOYS WASHROOM 164, LOW WATER PRESSURE AT HAND WASHING SINK IN KITCHEN, UNISEX WASHROOM NEAR JANITOR CLOSET 165 AND GIRLS WASHROOM 161. OBSERVED NO HOT WATER AT MIDDLE SINK IN GIRLS WASHROOM 163, LEFT SINK IN BOYS WASHROOM 164, MIDDLE SINK IN BOYS WASHROOM 286. INSTRUCTED MANAGER TO REPAIR AND MAINTAIN.
    • 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
      • OBSERVED NO COVERED RECEPTACLES IN GIRLS WASHROOM 185, 186, 243,270,287,342, WOMEN WASHROOM 244, 340 AND UNISEX WASHROOM NEAR JANITOR CLOSET 165. INSTRUCTED MANAGER TO PROVIDE COVERED RECEPTACLES IN ALL GIRLS, WOMEN AND UNISEX WASHROOMS.
    • 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
      • OBSERVED MISSING STALL DOOR IN GIRLS WASHROOM 163. INSTRUCTED MANAGER TO REPLACE MISSING STALL DOOR AND MAINTAIN.
    • 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
      • OBSERVED DEBRIS ON FLOORS, DUST BUILDUP ON CEILING VENTS, AND LINES BEHIND COOKING EQUIPMENT.INSTRUCTED MANAGER TO CLEAN AND MAINTAIN.
  2. Canvass

    7 infractions

    • 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
      • OBSERVED NO HOT RUNNING WATER AT HAND WASHING SINK IN MEN WASHROOM 250, BOYS WASHROOM 248 (76.6F), MEN WASHROOM 231 (77.1F), WOMEN WASHROOM 244 (75.5F), GIRLS WASHROOM 243 (75.3F). INSTRUCTED MANAGER TO PROVIDE HOT WATER AT ALL HAND WASHING SINKS FOR PROPER HAND WASHING. PRIORITY 7-38-030(C)
    • 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
      • TIMED FAUCET NOT FUNCTIONING PROPERLY AT MIDDLE SINK IN GIRLS WASHROOM 270. WATER MUST RUN CONTINUOUSLY FOR AT LEAST 15 SECONDS BEFORE REACTIVATING FAUCET.
    • 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
      • OBSERVED OVER 30 MICE DROPPINGS SCATTERED ON FLOOR ALONG WALLS AND CORNERS IN LUNCHROOM STAFF WASHROOM. INSTRUCTED MANAGER TO CALL AN EXTERMINATOR FOR SERVICE, CLEAN AND SANTIZE ALL AREAS. PRIORITY FOUNDATION 7-38-020(A)
    • 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
      • OBSERVED LEAKING DRAINPIPE UNDER 3-COMPARTMENT SINK NEAR UNUSED WALK-IN COOLERS, AND UNDER LEFT SINK IN BOYS WASHROOM 164, LOW WATER PRESSURE AT HAND WASHING SINK IN KITCHEN, UNISEX WASHROOM NEAR JANITOR CLOSET 165 AND GIRLS WASHROOM 161. OBSERVED NO HOT WATER AT MIDDLE SINK IN GIRLS WASHROOM 163, LEFT SINK IN BOYS WASHROOM 164, MIDDLE SINK IN BOYS WASHROOM 286. INSTRUCTED MANAGER TO REPAIR AND MAINTAIN.
    • 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
      • OBSERVED NO COVERED RECEPTACLES IN GIRLS WASHROOM 185, 186, 243,270,287,342, WOMEN WASHROOM 244, 340 AND UNISEX WASHROOM NEAR JANITOR CLOSET 165. INSTRUCTED MANAGER TO PROVIDE COVERED RECEPTACLES IN ALL GIRLS, WOMEN AND UNISEX WASHROOMS.
    • 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
      • OBSERVED MISSING STALL DOOR IN GIRLS WASHROOM 163. INSTRUCTED MANAGER TO REPLACE MISSING STALL DOOR AND MAINTAIN.
    • 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
      • OBSERVED DEBRIS ON FLOORS, DUST BUILDUP ON CEILING VENTS, AND LINES BEHIND COOKING EQUIPMENT.INSTRUCTED MANAGER TO CLEAN AND MAINTAIN.
  3. Canvass

    0 infraction

  4. Canvass

    2 infractions

    • 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
      • FOUND SOME FAUCETS AT HANDSINKS IN STUDENT WASHROOMS NOT STAYING ON THE REQUIRED MINIMUM TIME OF 15 SECONDS; MUST ADJUST FAUCETS WHERE NEEDED.
    • 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
      • FOUND STANDING WATER IN A WALK IN COOLER THAT WAS NOT WORKING; INSTRUCTED TO REMOVE STANDING WATER. (CORRECTED ON SITE) INSTRUCTED TO SWEEP IN CANTEEN AREA AND STORAGE AREA. (CORRECTED ON SITE)
  5. Canvass

    3 infractions

    • 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
      • FOUND SOME HANDSINKS IN VARIOUS STUDENT WASHROOMS THAT DO NOT STAY ON THE REQUIRED TIME OF 15 SECONDS; MUST ADJUST FAUCETS WHERE NEEDED.
    • 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
      • OBSERVED SOME FAUCETS IN STUDENT WASHROOMS THAT DO NOT WORK; MUST CORRECT BY REPAIRING FAUCETS OR PROVIDING BATTERIES FOR FAUCETS.
    • 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
      • INSTRUCTED TO CLEAN FLOORS IN KITCHEN UNDER SHELVES IN STORAGE AREAS, UNUSED WALK-IN COOLERS AND FRONT SERVING LINE.
  6. Canvass

    1 infraction

    • 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
      • INSTRUCTED TO CLEAN THE FLOOR IN THE CANTEEN ROOM BEHIND CART. (COS)
  7. Canvass Re-Inspection

    1 infraction

    • 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
      • MUST INCREASE WATER PRESSURE OF HOT RUNNING WATER FROM FAUCET AT HANDWASH SINK OF FOOD DISPENSING LINE.
  8. Canvass

    4 infractions

    • 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
      • NOTED NO HOT RUNNING WATER AT HANDWASHING SINKS OF 2ND FLOOR OF MID SECTION BOYS/GIRLS WASHROOMS. TEMPERATURE AT TIME OF INSPECTION RANGED FROM 74 F. INSTRUCTED THAT THE MINIMUM TEMPERATURE FOR HOT RUNNING WATER AT ALL HANDWASHING SINKS SHOULD BE 100F. PRIORITY VIOLATION 7-38-030(C).
    • 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
      • OBSERVED WALK-IN FREEZER AND 2 WALK-IN COOLERS IN POOR REPAIR AWAITING ORDERED PARTS TO COMPLETE REPAIRS. MUST REPAIR. ALSO NOTED(NEW) ICE MACHINE IN POOR REPAIR. MUST REPAIR.
    • 50. HOT & COLD WATER AVAILABLE; ADEQUATE PRESSURE
      • WATER AT HAND WASH SINK AT FOOD DISPENSING LINE NOT AT ADEQUATE PRESSURE. MUST PROVIDE WATER UNDER PRESSURE. PRIORITY VIOLATION 7-38-030(C).
    • 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
      • MUST PROVIDE COVERED LID FOR RECEPTACLE IN WASHROOM USED BY FEMALE STAFF.
  9. Canvass Re-Inspection

    2 infractions

    • 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
      • OBSERVED NO HAND WASH SINK AT FOOD DISPENSING LINE CONVENIENTLY FOR EMPLOYEES. MUST PROVIDE. PRIORITY FOUNDATION VIOLATION 7-38-030(C).
    • 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
      • MUST PROVIDE LIGHT BULB FOR ADEQUATE LIGHTING IN WALK-IN FREEZER.
  10. Canvass

    3 infractions

    • 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
      • OBSERVED NO HAND WASH SINK AT FOOD DISPENSING LINE CONVENIENTLY FOR EMPLOYEES. MUST PROVIDE. PRIORITY FOUNDATION VIOLATION 7-38-030(C).
    • 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
      • OBSERVED HAND SINK IN PREP AREA CLOGGED AND UNABLE TO DRAIN ADEQUATELY FOR PROPER HAND WASHING. MUST REPAIR. PRIORITY VIOLATION 7-38-030(C).
    • 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
      • MUST PROVIDE LIGHT BULB FOR ADEQUATE LIGHTING IN WALK-IN FREEZER.
  11. Canvass

    2 infractions

    • 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
      • Observed ice accumulation on floor of walk in freezer #2. Must defrost, clean and sanitize. Must maintain same.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • Observed hand sink on canteen side on prep table where cookies are cooling. Must install splash guard to prevent contamination. Must maintain same. Observed leak under midde and right basin of 3 compartment sink in kitchen. Must repair and maintain same. Observed leak from large water containment unit in basement (near pool pump). Must repair and maintain same.
  12. Canvass Re-Inspection

    1 infraction

    • 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
      • ORGANIZE 315 PREP ROOM TO PREVENT PEST HARBORAGE.
  13. Canvass Re-Inspection

    5 infractions

    • 14. PREVIOUS SERIOUS VIOLATION CORRECTED, 7-42-090
      • PREVIOUS SERIOUS VIOLATION NOT CORRECTED FROM REPORT #2009232 ON 3-24-17:18-OBSERVED 15 MICE DROPPINGS ON SINK BASIN, BOTTOM SHELVES AND LEDGES OF EQUIPMENT IN UNUSED SERVING LINE, 15 MICE DROPPINGS ON FLOOR IN UNUSED DISH MACHINE AREA, 15 MICE DROPPINGS IN CORNER ON SHELF UNDER STEAM TABLE, 2 MICE DROPPINGS ON BASE OF HOT HOLDING UNIT BEHIND SERVING LINE, 10 MICE DROPPINGS ON FLOOR IN CORNER OF VENDING MACHINE STORAGE IN LUNCHROOM, 20 MICE DROPPINGS ON FLOOR IN ELECTRICAL CLOSET IN LUNCHROOM, 20 MICE DROPPINGS ON FLOOR IN CORNER CLOSET OF TEACHERS LOUNGE, 10 MICE DROPPINGS ON FLOOR IN ELECTRICAL CLOSET NEAR BOYS WASHROOM 148, 10 MICE DROPPINGS ON FLOOR NEAR ELECTRICAL ROOM NEAR GYM,5 MICE DROPPINGS ON FLOOR IN ELECTRICAL CLOSET ACROSS FROM ROOM 110,5 MICE DROPPINGS ON FLOOR BETWEEN CARDBOARD BOXES IN GYM STORAGE, 10 MICE DROPPINGS SCATTERED ON FLOOR IN ELECTRICAL ROOMS NEAR 264 STORAGE, 5 MICE DROPPINGS INSIDE CABINET IN 315 PREP, 5 MICE DROPPINGS INSIDE CABINET UNDER SINK IN PREP ROOM 324, 30 MICE DROPPINGS ON FLOOR IN ELECTRICAL CLOSET NEAR SECOND FLOOR GYM. INSTRUCTED MANAGER TO CALL AN EXTERMINATOR FOR SERVICE, CLEAN AND SANITIZE ALL AREAS. EXIT #3 NOT RODENT PROOFED, 1/4" GAP ON BOTTOM OF DOORS. SEAL ALL OUTER OPENINGS ON DOORS TO PREVENT PEST ENTRY. 26-OBSERVED NO HOT/TEMPERED WATER IN GIRLS WASHROOM 143, BOYS WASHROOM 148, INADEQUATE SUPPLY OF HOT RUNNING WATER IN GIRLS WASHROOM 186. INSTRUCTED MANAGER TO PROVIDE HOT/TEMPERED WATER AT WASHBOWLS FOR PROPER HAND WASHING. CRITICAL VIOLATION 7-42-090
    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • CLEAN FLOORS UNDER ALL EQUIPMENT, ALONG WALLS AND IN ALL CORNERS IN ALL ELECTRICAL CLOSETS AND STORAGE AREAS.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • REPAIR CEILING AND REPLACE MISSING CEILING TILES IN PREP ROOM 315. REPLACE DAMAGED SOAP DISPENSER IN BOYS WASHROOM 164.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • REPAIR SECOND FLOOR UTILITY SINK(NOT DRAINING).
    • 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
      • ORGANIZE 315 PREP ROOM TO PREVENT PEST HARBORAGE.
  14. Canvass

    8 infractions

    • 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
      • OBSERVED 15 MICE DROPPINGS ON BOTTOM SHELVES AND LEDGES OF UNUSED SERVING LINE, 15 MICE DROPPINGS ON FLOOR IN UNUSED DISH MACHINE AREA, 15 MICE DROPPINGS IN CORNER ON SHELF UNDER STEAM TABLE, 2 MICE DROPPINGS ON BASE OF HOT HOLDING UNIT BEHIND SERVING LINE, 10 MICE DROPPINGS ON FLOOR IN CORNER OF VENDING MACHINE STORAGE IN LUNCHROOM, 20 MICE DROPPINGS ON FLOOR IN ELECTRICAL CLOSET IN LUNCHROOM, 20 MICE DROPPINGS ON FLOOR IN CORNER CLOSET OF TEACHERS LOUNGE, 10 MICE DROPPINGS ON FLOOR IN ELECTRICAL CLOSET NEAR BOYS WASHROOM 148, 10 MICE DROPPINGS ON FLOOR NEAR ELECTRICAL ROOM NEAR GYM,5 MICE DROPPINGS ON FLOOR IN ELECTRICAL CLOSET ACROSS FROM ROOM 110,5 MICE DROPPINGS ON FLOOR BETWEEN CARDBOARD BOXES IN GYM STORAGE,10 MICE DROPPINGS SCATTERED ON BOTTOM SURFACES OF POPCORN MACHINE IN STAIRWAY NEAR 264 STORAGE, 5 MICE DROPPINGS INSIDE CABINET IN 315 PREP, 5 MICE DROPPINGS INSIDE CABINET UNDER SINK IN PREP ROOM 324, 30 MICE DROPPINGS ON FLOOR IN ELECTRICAL CLOSET NEAR SECOND FLOOR GYM. INSTRUCTED MANAGER TO CALL AN EXTERMINATOR FOR SERVICE, CLEAN AND SANITIZE ALL AREAS. EXIT #3 NOT RODENT PROOFED, 1/4" GAP ON BOTTOM OF DOORS. SEAL ALL OUTER OPENINGS ON DOORS TO PREVENT PEST ENTRY. SERIOUS VIOLATION 7-38-020
    • 26. ADEQUATE NUMBER, CONVENIENT, ACCESSIBLE, PROPERLY DESIGNED AND INSTALLED
      • OBSERVED NO HOT/TEMPERED WATER AT MEN STAFF WASHROOM SECOND FLOOR, BOYS WASHROOM 248, WOMEN STAFF WASHROOM 244, GIRLS WASHROOM 143, BOYS WASHROOM 148, GIRLS WASHROOM 254, BOYS WASHROOM 256, MAIN OFFICE WASHROOMS, INADEQUATE SUPPLY OF HOT RUNNING WATER IN GIRLS WASHROOM 186. INSTRUCTED MANAGER TO PROVIDE HOT/TEMPERED WATER AT WASHBOWLS FOR PROPER HAND WASHING. SERIOUS VIOLATION 7-38-030
    • 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
      • CLEAN INTERIOR OF ICE MACHINE IN KITCHEN.
    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • CLEAN FLOORS UNDER ALL EQUIPMENT, ALONG WALLS AND IN ALL CORNERS IN ALL ELECTRICAL CLOSETS AND STORAGE AREAS.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • REPLACE MISSING CEILING TILES IN KITCHEN NEAR OFFICE. REPAIR CEILING AND REPLACE MISSING CEILING TILES IN PREP ROOM 315. REPLACE DAMAGED SOAP DISPENSER IN BOYS WASHROOM 164.
    • 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
      • SECURE LOOSE LIGHT SHIELD NEAR 3-COMPARTMENT SINK. REPLACE DAMAGED LIGHT SHIELD IN WALK-IN FREEZER NEAR 3-COMPARTMENT SINK.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • REPAIR LEAKING FAUCET ON SINK IN MAIN OFFICE WASHROOM. REPAIR SECOND FLOOR UTILITY SINK(NOT DRAINING).
    • 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
      • ORGANIZE 315 PREP ROOM TO PREVENT PEST HARBORAGE.
  15. Canvass Re-Inspection

    0 infraction

  16. Canvass

    3 infractions

    • 26. ADEQUATE NUMBER, CONVENIENT, ACCESSIBLE, PROPERLY DESIGNED AND INSTALLED
      • FOUND NO HOT RUNNING WATER IN FOUR STUDENT WASHROOMS ON THE SECOND AND THIRD FLOORS (BOYS #270, GIRLS #271, BOYS #343 AND GIRLS #342. MIXING VALVES ON ALL SINKS. INSTRUCTED THAT THE TEMPERATURE SHOULD BE 85F AS DEFINED BY THE INTERNATIONAL PLUMBING CODE. (TEMPS FOUND AT THIS TIME RANGED FROM 55.8F-77.3F). SERIOUS VIOLATION 7-38-030.
    • 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
      • CLEAN INTERIOR PANEL OF ICE MACHINE.
    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • CLEAN FLOORS IN STORAGE ROOMS OF KITCHEN.
  17. Canvass Re-Inspection

    6 infractions

    • 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
      • Inspector Comments: MUST REMOVE RUST FROM SHELVING UNITS IN WALK IN FREEZER AND DRY FOOD STORAGE AREA.MUST REPLACE OR REPAIR MISSING FAN GUARD COVER IN WALK IN FREEZER#2,LOOSE DOOR HANDLE ON HOT HOLDING CABINET.
    • 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
      • Inspector Comments: MUST CLEAN DEBRI FROM INTERIOR OF HOT HOLDING CABINET,MICROWAVES,LOWER SHELVES OF PREP TABLE OF 1- COMP SINK,SERVING LINE EQUIPMENT.MUST DEFROST ICE BUILD UP FROM MILK COOLER ON SERVING LINE.MUST REMOVE CALCIUM BUILD UP AT ALL FAUCETS AT 1- COMP & 3- COMP SINKS.
    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • Inspector Comments: MUST CLEAN FLOOR ALONG WALL BASES IN MOTOR ROOM.MUST REPAIR OR REPLACE DAMAGED FLOOR TILES IN WALK IN FREEZER,ICE BUILD UP FROM FLOOR IN WALK IN FREEZER #2
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • Inspector Comments: MUST REPAIR OR REPLACE MISSING AND DAMAGED WALLTILES AND DOOR TRIMS OF WALK IN COOLERS AND FREEZERS.MUST CLEAN DUST BUILD UP ON WALLS ,WINDOW SILLS ,FILTERS IN PREP AREA
    • 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
      • Inspector Comments: MUST REPLACE BURNT OUT LIGHTS IN PREP AREA.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • Inspector Comments: MUST REMOVE ICE BUILD UP FROM COMPRESSOR UNIT IN WALK IN PRODUCE COOLER.MUST REPAIR OR REPLACE LEAKY FAUCETS AND PIPES AT 1- COMP & 3- C0MP SINKS.
  18. Canvass

    7 infractions

    • 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
      • OBSERVED EVIDENCE OF APPX. 100 OR MORE RODENT DROPPINGS ON FLOOR IN LUNCHROOM ELECTRICAL PANEL ROOM AND STORAGE ROOM NEAR SHELVING UNIT,MOTOR ROOM ALONG WALL BASES ,TEACHER LOUNGE UNUSED EQUIPMENT ON SERVING LINE.ALSO LIVE ROACH ACTIVITY IN FLOOR DRAINS UNDER HOOD OF COOKING EQUIPMENT AND POT STORAGE AREA.ALSO DOORS NOT RODENT PROOFED #1,3,5,7, & 8.MUST REMOVE DROPPINGS CLEAN AND SANITIZE AREAS,RODENT PROOF DOORS.RECOMMENDED TO HAVE A PEST CONTROL OPERATOR TO SERVICE PREMISES ON OR AFTER 3/23/15.(SERIOUS 7-38-020)NO CITATION ISSUED.
    • 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
      • MUST REMOVE RUST FROM SHELVING UNITS IN WALK IN FREEZER AND DRY FOOD STORAGE AREA.MUST REPLACE OR REPAIR MISSING FAN GUARD COVER IN WALK IN FREEZER#2,LOOSE DOOR HANDLE ON HOT HOLDING CABINET.
    • 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
      • MUST CLEAN DEBRI FROM INTERIOR OF HOT HOLDING CABINET,MICROWAVES,LOWER SHELVES OF PREP TABLE OF 1- COMP SINK,SERVING LINE EQUIPMENT.MUST DEFROST ICE BUILD UP FROM MILK COOLER ON SERVING LINE.MUST REMOVE CALCIUM BUILD UP AT ALL FAUCETS AT 1- COMP & 3- COMP SINKS.
    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • MUST CLEAN FLOOR ALONG WALL BASES IN MOTOR ROOM.MUST REPAIR OR REPLACE DAMAGED FLOOR TILES IN WALK IN FREEZER,ICE BUILD UP FROM FLOOR IN WALK IN FREEZER #2.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • MUST REPAIR OR REPLACE MISSING AND DAMAGED WALLTILES AND DOOR TRIMS OF WALK IN COOLERS AND FREEZERS.MUST CLEAN DUST BUILD UP ON WALLS ,WINDOW SILLS ,FILTERS IN PREP AREA.
    • 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
      • MUST REPLACE BURNT OUT LIGHTS IN PREP AREA.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • MUST REMOVE ICE BUILD UP FROM COMPRESSOR UNIT IN WALK IN PRODUCE COOLER.MUST REPAIR OR REPLACE LEAKY FAUCETS AND PIPES AT 1- COMP & 3- C0MP SINKS.
  19. Canvass

    4 infractions

    • 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
      • MUST CLEAN AND MAINTAIN INTERIOR PANEL OF ICE MACHINE.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • MUST CORRECT THE FOLLOWING VIOLATIONS: REPLACE DAMAGED CEILING TILE IN FACULTY WASHROOM ON THIRD FLOOR #345. CLEAN CEILING VENTS IN WASHROOMS WHERE NEEDED TO REMOVE DUST. REPLACE CEILING TILES IN HALLWAYS WHERE NEEDED. REPLACE WALL TILES IN WALK-IN COOLERS WHERE NEEDED; WALK-IN UNITS 1,2 AND 3.
    • 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
      • PROVIDE A LIGHT BULB FOR LIGHT IN WALK-IN FREEZER ACROSS FROM ICE MACHINE IN KITCHEN.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • MUST UNCLOG ONE SINK IN GIRLS WASHROOM ON SECOND FLOOR #254 (TWO ADDITIONAL SINKS IN WASHROOM). MUST REPLACE MISSING FAUCET KNOB AT ONE SINK IN GIRLS WASHROOM ON FIRST FLOOR #163.
  20. Canvass

    4 infractions

    • 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
      • MUST REMOVE RUST FROM STORAGE SHELVES IN THE DRY STORAGE ROOM OR REPLACE. MAY PAINT SHELVES WITH A LIGHT COLORED NON TOXIC PAINT. MUST REMOVE ICE BUILD UP ON THE INTERIOR OF THE WALK IN FREEZER.
    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • MUST REMOVE WATER FROM FLOORS IN THE BOILER ROOM.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • MUST REPAIR THE LEAKY FAUCETS AT THE THREE COMPARTMENT SINKS IN THE PREP AREA. MUST ALSO REPAIR THE LEAKY FAUCET AT THE MOP SINK IN THE KITCHEN. MUST REPAIR LEAKY FAUCET AT THE MOP SINK IN CLOSET 248 (BUILDING B) AND IN THE BOILER ROOM. MUST REPAIR OVERHEAD LEAKS IN THE BOILER ROOM.
    • 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
      • MUST BETTER ORGANIZE CLUTTER IN THE OLD DISH MACHINE ROOM.
  21. Canvass

    6 infractions

    • 31. CLEAN MULTI-USE UTENSILS AND SINGLE SERVICE ARTICLES PROPERLY STORED: NO REUSE OF SINGLE SERVICE ARTICLES
      • INVERT PLASTIC SPOONS ON SERVING LINES TO PROTECT FROM CONTAMINATION.
    • 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
      • REMOVE MILK CRATES OFF FLOOR AND PROVIDE ADEQUATE SHELVING IN WALK-IN FREEZER. REPAIR INOPERABLE WALK-IN FREEZER. REPLACE DAMAGED DOOR SWEEPS.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • REPLACE STAINED CEILING TILES IN SECOND FLOOR UTILITY CLOSET.
    • 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
      • PROVIDE LIGHT SHIELDS IN WALK-IN COOLER AND FREEZER.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • PROVIDE HOT WATER AT SINK IN MEN SECOND FLOOR STAFF WASHROOM. INCREASE HOT WATER PRESSURE AT SINK IN OFFICE BREAK ROOM. REPAIR LEAKS IN BOILER ROOM.
    • 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
      • REMOVE UNUSED EQUIPMENT AND UNNECESSARY ARTICLES IN GYM STORAGE AREAS TO PREVENT PEST HARBORAGE.
  22. Canvass Re-Inspection

    0 infraction

  23. Canvass

    2 infractions

    • 29. PREVIOUS MINOR VIOLATION(S) CORRECTED 7-42-090
      • FOUND PREVIOUS MINOR VIOLATION NOT CORRECTED. FOUND RUSTY SHELVES IN WALK IN COOLERS. MUST SEAL OR REPLACE SHELVES. FROM REPORT DATED 6-1-2010 # 74470. SERIOUS VIOLATION. CITATION ISSUED.
    • 31. CLEAN MULTI-USE UTENSILS AND SINGLE SERVICE ARTICLES PROPERLY STORED: NO REUSE OF SINGLE SERVICE ARTICLES
      • FOUND FOOD CONTAINERS NOT STORED PROPERLY. MUST STORE INVERTED.
  24. Canvass

    5 infractions

    • 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
      • RUSTY SHELVES IN WALK-IN COOLERS, SEAL WITH A NON-TOXIC PAINT OR REPLACE SHELVES
    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • DETAIL CLEAN FLOORS IN COOLERS UNDER ALL SHELVES, AND CORNERS THROUGHOUT.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • SEAL ALL CRACKS AND HOLES ON WALLS PREVENTING ANY INSECT ENTRANCE AND HORBAGE THROUGHOUT.
    • 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
      • DETAIL CLEAN ALL LIGHT SHIELDS THROUGHOUT.
    • 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
      • CLUTTER IN OLD DISHWASHER ROOM ORGANIZE.