Skip to content
Loading map…

Ascent Canmore - Whirlpool

1730 Bow Valley Trail Canmore AB T1W 2X3 · Aquatic Facility

2 inspections

  1. Initial Inspection

    0 infractions

  2. Demand Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free chlorine was measured as 1.72ppm. Controller was calibrated and free chlorine was measured as 4.59ppm by end of inspection.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate for the whirlpool was only 175gpm. Minimum required flow rate is 193gpm. Pump speed adjusted, flow rate increased to 202gpm.