Pocaterra Inn and Waterslide - Swimming Pool
1725 Bow Valley Trail Canmore AB T1W 2W1 · Aquatic Facility
17 inspections
- Demand Inspection
0 infractions
- Demand Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Outstanding Violation*There was a leak coming from the pool filter. - Please repair the leak, ensure the circulation system is in good repair.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday March 24th, 2025, had a HPC of 1,020 CFU/ml. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a leak coming from the pool filter. - Please repair the leak, ensure the circulation system is in good repair.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday March 3rd, 2025, had a HPC of 240 CFU/ml. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a leak coming from the pool filter. - Please repair the leak, ensure the circulation system is in good repair.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a leak coming from the pool filter. - Please repair the leak, ensure the circulation system is in good repair.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a leak coming from the pool filter. - Please repair the leak, ensure the circulation system is in good repair.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeat Violation**The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was low, 27 ppm. - Raise the alkalinity, ensure it is maintained in the 60-180 ppm range.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was measured as 2ppm and there was a strong "chloramine" smell in the pool area. Combined chlorine level in the pool water to be reduced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- *Please ensure combined chlorine levels are tested daily*Does not appear the combined chlorine level is being tested. In the pool logs (approximately 3 weeks of entries were present) the combined chlorine was written as 0ppm every time and when tested today using the pool operator's testing kit, measured as 1ppm. Combined chlorine level is to be tested daily.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was low, 27 ppm. - Raise the alkalinity, ensure it is maintained in the 60-180 ppm range.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was measured as 2ppm and there was a strong "chloramine" smell in the pool area. Combined chlorine level in the pool water to be reduced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Does not appear the combined chlorine level is being tested. In the pool logs (approximately 3 weeks of entries were present) the combined chlorine was written as 0ppm every time and when tested today using the pool operator's testing kit, measured as 1ppm. Combined chlorine level is to be tested daily.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- October 28, 2024 water sample had a plate count of 270cfu/ml. Treat water to remove contamination. Resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was low, 33 ppm. - Raise the alkalinity, ensure it is maintained in the 60-180 ppm range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was low, 33 ppm. - Raise the alkalinity, ensure it is maintained in the 60-180 ppm range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample received 7/26/2024 was not processed by the lab, date on the form indicated it was received more than 24 hrs. after collection. Operators were informed to submit a re-sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was low, 41ppm. - Raise the alkalinity, ensure it is maintained in the 60-180 ppm range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow rate could not be determined for the waterslide pump as the float was stuck in the flow meter. Please repair the flow meter for the waterslide pump.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was low, 41ppm. - Raise the alkalinity, ensure it is maintained in the 60-180 ppm range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow rate could not be determined for the waterslide pump as the float was stuck in the flow meter. Please repair the flow meter for the waterslide pump.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday June 3rd, 2024, had an HPC of 390 cfu/ml. - Operators were informed to treat and re-sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was low, 41ppm. - Raise the alkalinity, ensure it is maintained in the 60-180 ppm range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow rate could not be determined for the waterslide pump as the float was stuck in the flow meter. Please repair the flow meter for the waterslide pump.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity was low, 41ppm. - Raise the alkalinity, ensure it is maintained in the 60-180 ppm range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmers are missing floating weirs. - Ensure all skimmers have floating weirs to maximize flow through the skimmers.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow rate could not be determined for the waterslide pump as the float was stuck in the flow meter. Please repair the flow meter for the waterslide pump.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?