Comfort Inn - Pool

203 19 Avenue Nisku AB T9E 0W8 · Aquatic Facility

16 inspections

  1. Monitoring Inspection

    0 infractions

  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total Coliforms present in a sample collected on April 16/2025.The manager was directed to shock chlorinate the pool and resample after.
  4. Monitoring Inspection

    0 infractions

  5. Risk Management Inspection

    0 infractions

  6. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • ** The operator is not properly documenting pool chemistry records:- Example: On March 26/2024, pool chemistry was documented as follows: Free chlorine-1.32ppm; Total chlorine-0.03ppm and Combine chlorine - 1.29ppm. ** Total chlorine cannot be less than free chlorine because total chlorine is the sum of free and combine chlorine**. This practice was observed during past inspections and consistent in the March, April and May records.- Pool chemistry is not checked and documented after manual addition of chemicals in the pool.- There are no time stamps on the pool chemistry recordsACTION REQUIRED:1) Ensure that pool chemistry is properly documented.2) Ensure that a follow up pool chemistry test is done after manual addition of chemicals in the pool3) Ensure that the time pool test was conducted is documented on the records.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Three consecutive failed water samples with HPC >100. The operator temporally closed the pool until a satisfactory water result is achieved.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • ** The operator is not properly documenting pool chemistry records:- Example: On March 26/2024, pool chemistry was documented as follows: Free chlorine-1.32ppm; Total chlorine-0.03ppm and Combine chlorine - 1.29ppm. ** Total chlorine cannot be less than free chlorine because total chlorine is the sum of free and combine chlorine**. This practice was observed during past inspections and consistent in the March, April and May records.- Pool chemistry is not checked and documented after manual addition of chemicals in the pool.- There are no time stamps on the pool chemistry recordsACTION REQUIRED:1) Ensure that pool chemistry is properly documented.2) Ensure that a follow up pool chemistry test is done after manual addition of chemicals in the pool3) Ensure that the time pool test was conducted is documented on the records.
  8. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Two consecutive water samples with HPC present. Sample on April 24 had >5700HPC. Pool to be treated before re-opened to the public.
  9. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 490 HPC present in a sample submitted on April 19
  10. Monitoring Inspection

    0 infractions

  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 120 HPC in a sample submitted on November 22
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • ** Daily pool chemistry logs were missing from February 30/2023. - Ensure that pool chemistry is checked and documented daily.
  12. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • ** Daily pool chemistry logs were missing from February 30/2023. - Ensure that pool chemistry is checked and documented daily.
  13. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC present in a sample submitted on September 19th.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • ** Daily pool chemistry logs were missing from February 30/2023. - Ensure that pool chemistry is checked and documented daily.
  14. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • ** Daily pool chemistry logs were missing from February 30/2023. - Ensure that pool chemistry is checked and documented daily.
  15. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC present in a water sample submitted on July 18. Operator directed to shock chlorinate and resample.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • ** Daily pool chemistry logs were missing from February 30/2023. - Ensure that pool chemistry is checked and documented daily.
  16. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • ** Daily pool chemistry logs were missing from February 30/2023. - Ensure that pool chemistry is checked and documented daily.