Days Inn Innisfail - Whirlpool

5010 40 Avenue Innisfail AB T4G 1Z1 · Aquatic Facility

12 inspections

  1. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following water testing reagents were observed to be past their best before dates.-Thiosulphate CR 0007 (Feb 2025).-pH indicator CR 0004(Dec 2024)-Total Alkalinity CR-0008 (May 2025)**Please have these reagents replace to ensure accurate testing of water chemistry parameters.
  2. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free available chlorine = 1.85ppm.**Please adjust water chemistry to ensure FAC is maintained at above 2.0ppm.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Daily water chemistry testing records are not being adequately maintained. There were no dates/ time on the recent records observed in the file.**Please ensure adequate records are kept at all times.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following water testing reagents were observed to be past their best before dates.-Thiosulphate CR 0007 (Feb 2025).-pH indicator CR 0004(Dec 2024)-Total Alkalinity CR-0008 (May 2025)**Please have these reagents replace to ensure accurate testing of water chemistry parameters.
  3. Monitoring Inspection

    0 infractions

  4. Risk Management Inspection

    0 infractions

  5. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free Available Chlorine: 1.13 ppmNote: Please adjust/add more chlorine to the whirlpool to meet the requirements of 2.0 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The rate of filtration is 15.3 GPM/sq ft. Note: The filtration rate does not meet the manufacturers (maximum 74 GPM with 15 GPM/sq ft.) and legislative requirements.Please adjust the flow rate 60 GPM to meet the requirements.
  6. Risk Management Inspection

    0 infractions

  7. Monitoring Inspection

    0 infractions

  8. Demand Inspection

    0 infractions

  9. Risk Management Inspection

    0 infractions

  10. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas isolated.The hot tub must be drained, cleaned, and disinfected and the filter cleaned and disinfected (or replaced). Refill the hot tub and bring disinfectant residuals back to normal levels.
  11. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Pseudomonas isolated.The hot tub must be drained, cleaned, and disinfected and the filter cleaned and disinfected (or replaced). Refill the hot tub and bring disinfectant residuals back to normal levels.
  12. Monitoring Inspection

    0 infractions