Four Points by Sheraton Grande Prairie - Pool
6702 106 Street Grande Prairie AB T8W 0K8 · Aquatic Facility
17 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on June, 17, 2026 indicates HPC>57000 CFU/mL.Ensure pool is super chlorinated and water is balanced prior to opening.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH was noted to be 7.72.The operator added muriatic acid to lower the pH and noted as 7.6 through operator's kit.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory result received, collection date August 27, 2025 - HPC >57 000 CFU/ml.Shock chlorinate and resample the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date July 2, 2025.- HPC >57 000 CFU/mlSuperchlorinate and resample the pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The sand filter is leaking from the cap.Repair the leak and ensure the sand filters are maintained in good repair. The parts are on order as per pool operator.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date July 2, 2025.- HPC >57 000 CFU/mlSuperchlorinate and resample the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory sample received, collection date June 9, 2025 - HPC 1150 CFU/ml.Resample the pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The sand filter is leaking from the cap.Repair the leak and ensure the sand filters are maintained in good repair. The parts are on order as per pool operator.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory sample received, collection date April 9, 2025 - HPC >57000 CFU/ml.Resample the pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The sand filter is leaking from the cap.Repair the leak and ensure the sand filters are maintained in good repair. The parts are on order as per pool operator.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The sand filter is leaking from the cap.Repair the leak and ensure the sand filters are maintained in good repair. The parts are on order as per pool operator.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- According to the pool anti-entrapment plan the submerged outlet covers expired on November 5, 2022. Please verify and replace the outlet covers. Please ensure to maintain documentation regarding any maintenance to the pool basin including the replacement of outlet covers.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity is noted at 50 ppm and 43 ppm. Please ensure the alkalinity is maintained at 60 to 180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Unable to calculate the turnover rate and verify the flow rate as the flow rate meter is installed upside down.Please install the flow rate meter upright and verify the flow rate to ensure the turnover rate meets legislative requirements.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- According to the pool anti-entrapment plan the submerged outlet covers expired on November 5, 2022. Please verify and replace the outlet covers. Please ensure to maintain documentation regarding any maintenance to the pool basin including the replacement of outlet covers.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover rate was calculated to be 6.225 hours. Please adjust the flow rate to ensure 100% of the pools water passes through re-circulation and treatment system within 4 hours.The turnover cannot be calculated as the flow rate meter is not working. The turnover rate can be calculated by:Volume of the pool/Turnover rate/ 60 mins.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate meter was not working.Please repair the flow rate meter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The shower before entering the poo/hot sign is missing. Please install the indicated sign as a reminder to bathers to shower before pool/ hot tub use.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The laboratory report indicated total coliforms present in the pool.Please super chlorinate the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC is noted at 57000 CFU/ml.Please super chlorinate the pool. A second unsatisfactory laboratory report was received.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover rate was calculated to be 6.225 hours. Please adjust the flow rate to ensure 100% of the pools water passes through re-circulation and treatment system within 4 hours.The turnover cannot be calculated as the flow rate meter is not working. The turnover rate can be calculated by:Volume of the pool/Turnover rate/ 60 mins.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate meter was not working.Please repair the flow rate meter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The shower before entering the poo/hot sign is missing. Please install the indicated sign as a reminder to bathers to shower before pool/ hot tub use.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC is noted at 57000 CFU/ml.Please super chlorinate the pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover rate was calculated to be 6.225 hours. Please adjust the flow rate to ensure 100% of the pools water passes through re-circulation and treatment system within 4 hours.The turnover cannot be calculated as the flow rate meter is not working. The turnover rate can be calculated by:Volume of the pool/Turnover rate/ 60 mins.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate meter was not working.Please repair the flow rate meter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The shower before entering the poo/hot sign is missing. Please install the indicated sign as a reminder to bathers to shower before pool/ hot tub use.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC is noted at 57000 CFU/ml.Please super chlorinate the pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover rate was calculated to be 6.225 hours. Please adjust the flow rate to ensure 100% of the pools water passes through re-circulation and treatment system within 4 hours.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?