Four Points by Sheraton Grande Prairie - Pool

6702 106 Street Grande Prairie AB T8W 0K8 · Aquatic Facility

16 inspections

  1. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • A microbiological water sample was collected on August 12, 2026 and submitted to the regional health authority for analysis. The results from this sample indicate >57,000 cfu/mL of HPC.The owner / operator of this facility is requested to conduct the following, namely:1. Super chlorinate and then re-balance this pool basin and re-sample this week (i.e. Tuesday or Wednesday) to verify the results.
  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on July 21, 2026, indicates HPC at 20 CFU/mL.Water sample collected on July 22, 2026, indicates HPC at 1080 CFU/mL.Ensure pool is super chlorinated and water is balanced prior to opening.
  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on June, 17, 2026 indicates HPC>57000 CFU/mL.Ensure pool is super chlorinated and water is balanced prior to opening.
  4. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH was noted to be 7.72.The operator added muriatic acid to lower the pH and noted as 7.6 through operator's kit.
  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory laboratory result received, collection date August 27, 2025 - HPC >57 000 CFU/ml.Shock chlorinate and resample the pool.
  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory water result received, collection date July 2, 2025.- HPC >57 000 CFU/mlSuperchlorinate and resample the pool.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The sand filter is leaking from the cap.Repair the leak and ensure the sand filters are maintained in good repair. The parts are on order as per pool operator.
  8. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory water result received, collection date July 2, 2025.- HPC >57 000 CFU/mlSuperchlorinate and resample the pool.
  9. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory laboratory sample received, collection date June 9, 2025 - HPC 1150 CFU/ml.Resample the pool.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The sand filter is leaking from the cap.Repair the leak and ensure the sand filters are maintained in good repair. The parts are on order as per pool operator.
  10. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unsatisfactory laboratory sample received, collection date April 9, 2025 - HPC >57000 CFU/ml.Resample the pool.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The sand filter is leaking from the cap.Repair the leak and ensure the sand filters are maintained in good repair. The parts are on order as per pool operator.
  11. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The sand filter is leaking from the cap.Repair the leak and ensure the sand filters are maintained in good repair. The parts are on order as per pool operator.
  12. Risk Management Inspection

    0 infractions

  13. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • According to the pool anti-entrapment plan the submerged outlet covers expired on November 5, 2022. Please verify and replace the outlet covers. Please ensure to maintain documentation regarding any maintenance to the pool basin including the replacement of outlet covers.
  14. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity is noted at 50 ppm and 43 ppm. Please ensure the alkalinity is maintained at 60 to 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Unable to calculate the turnover rate and verify the flow rate as the flow rate meter is installed upside down.Please install the flow rate meter upright and verify the flow rate to ensure the turnover rate meets legislative requirements.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • According to the pool anti-entrapment plan the submerged outlet covers expired on November 5, 2022. Please verify and replace the outlet covers. Please ensure to maintain documentation regarding any maintenance to the pool basin including the replacement of outlet covers.
  15. Risk Management Inspection

    0 infractions

  16. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover rate was calculated to be 6.225 hours. Please adjust the flow rate to ensure 100% of the pools water passes through re-circulation and treatment system within 4 hours.The turnover cannot be calculated as the flow rate meter is not working. The turnover rate can be calculated by:Volume of the pool/Turnover rate/ 60 mins.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate meter was not working.Please repair the flow rate meter.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The shower before entering the poo/hot sign is missing. Please install the indicated sign as a reminder to bathers to shower before pool/ hot tub use.