Four Points by Sheraton Grande Prairie - Whirlpool
6702 106 Street Grande Prairie AB T8W 0K8 · Aquatic Facility
30 inspections
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. Water sample(s) collected on June 17, 2026, indicated the presence of Pseudomonas aeruginosa.2. Water sample collected on June 17, 2026, indicated the presence of Total Coliforms.Ensure hot tub remains closed until satisfactory water results are received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample(s) collected on June 17, 2026, indicated the presence of HPC >57000 CFU/mL.Ensure hot tub remains closed until satisfactory water results are received.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- For water sample collected on May 27, 2026, Lab results indicate: Pseudomonas aeruginosa - Isolated.Ensure hot tub remains closed until satisfactory water results are received.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received, collection date May 27, 2026; Total Coliforms - Present.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample(s) (27-05-2026) result(s) indicates HPC > 57000 CFU / mL.Ensure hot tub remains closed until satisfactory results are received
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received, collection date May 27, 2026; Total Coliforms - Present.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received, collection date November 12, 2025; Pseudomonas - Isolated.Temporarily close the hot tub, backwash, super chlorinate for 4 -6 hours, drain,scrub the hot tub and submit a water sample. Follow the directions as indicated in the "Pseudomonas information sheet". The information sheet will be sent with the report in an email.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory result received, collection date November 12, 2025 - HPC > 57 000 CFU/ml.Superchlorinate the hot tub.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory result received, collection date August 27, 2025 - HPC >57 000 CFU/ml.Shock chlorinate and resample the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date July 23, 2025: HPC >57000 CFU/ml. Superchlorinate the pool and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received, collection date June 4, 2025; Pseudomonas - Isolated.Temporarily close the hot tub, backwash, super chlorinate for 4 -6 hours, drain,scrub the hot tub and submit a water sample. Follow the directions as indicated in the "Pseudomonas information sheet". The information sheet will be sent with the report in an email.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date June 4, 2025: HPC >57000 CFU/ml. Superchlorinate the pool and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received, collection date April 22, 2025: Pseudomonas Aeruginosa - Isolated.Close the hot tub, backwash, super chlorinate for 4 -6 hours, drain, scrub the hot tub and resubmit another water sample. Hot tub to remain closed until a satisfactory water result is obtained. Please follow the directions as indicated in the "Pseudomonas information sheet". The information sheet will be sent with the report in an email.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date April 22, 2025: HPC 450 CFU/ml. Super chlorinate and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received, collection date April 15, 2025: Pseudomonas Aeruginosa - Isolated.Temporarily close the hot tub, backwash, super chlorinate for 4 -6 hours, drain,scrub the hot tub and submit a water sample. Please follow the directions as indicated in the "Pseudomonas information sheet". The information sheet will be sent with the report in an email.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date April 15, 2025: HPC 2400 CFU/ml. Super chlorinate the pool and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The Free available chlorine is noted at 0.47 ppm, ORP at 720 mV.Ensure the Free available chlorine is a minimum of 0.5 ppm if the ORP is equal to or great than 700 mV. The pool operator adjusted the free available chlorine during the inspection, and it measured 3.98 ppm with the pool operator kit.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory report received; collection date August 26, 2024 - HPC 120 CFU/ml.Please submit resample the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory laboratory results received from July 29, 2024: Pseudomonas Isolated. Please backwash, super chlorinate, run water through circulation 4 to 6 hours, drain, scrub with acid/sanitizer, rinse, refill pool, adjust chemistry and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory results received from July 29, 2024: HPC 57 000 CFU/mL.Please super chlorinate the pool and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory laboratory results received from June 25, 2024: Pseudomonas Isolated. Please backwash, super chlorinate, run water through circulation 4 to 6 hours, drain, scrub with acid/sanitizer, rinse, refill pool, adjust chemistry and resample. Manager indicated the hot tub would remain closed until pool operator conducts treatment.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory results received from June 25, 2024: HPC 57 000 CFU/mL.Please super chlorinate the pool and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The chlorine dispensing tube is in disrepair preventing proper dispensing of chlorine into the hot tub. Please repair the dispensing tube, monitor the FAC in the hot tub closely. The operator already has the part on order.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The chlorine dispensing tube is in disrepair preventing proper dispensing of chlorine into the hot tub. Please repair the dispensing tube, monitor the FAC in the hot tub closely. The operator already has the part on order.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- According to the hot tub anti entrapment plan the outlet covers expired November 5, 2022. Please verify the covers and replace the outlet covers as required. Please ensure to maintain documentation regarding any maintenance to the pool basin including the replacement of outlet covers. Manager has the parts on order.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory result received HPC 1010 CFU/ml.Please submit a resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The chlorine dispensing tube is in disrepair preventing proper dispensing of chlorine into the hot tub. Please repair the dispensing tube, monitor the FAC in the hot tub closely. The operator already has the part on order.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- According to the hot tub anti entrapment plan the outlet covers expired November 5, 2022. Please verify the covers and replace the outlet covers as required. Please ensure to maintain documentation regarding any maintenance to the pool basin including the replacement of outlet covers. Manager has the parts on order.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The chlorine dispensing tube is in disrepair preventing proper dispensing of chlorine into the hot tub. Please repair the dispensing tube, monitor the FAC in the hot tub closely. The operator already has the part on order.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- According to the hot tub anti entrapment plan the outlet covers expired November 5, 2022. Please verify the covers and replace the outlet covers as required. Please ensure to maintain documentation regarding any maintenance to the pool basin including the replacement of outlet covers. Manager has the parts on order.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The FAC is notes at 0.31 and 0.28 ppm.Please ensure the FAC is maintained at a minimum of 2.0 ppm in a hot tub.The operator added chlorine to the hot tub manually, and the FAC measured above 3.0 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The chlorine dispensing tube is in disrepair preventing proper dispensing of chlorine into the hot tub. Please repair the dispensing tube, monitor the FAC in the hot tub closely. The operator already has the part on order.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- According to the hot tub anti entrapment plan the outlet covers expired November 5, 2022. Please verify the covers and replace the outlet covers as required. Please ensure to maintain documentation regarding any maintenance to the pool basin including the replacement of outlet covers.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Laboratory results indicate Pseudomonas aeruginosa "isolated". Please close the hot tub and do the following:-backwash-superchlorinate for 4 -6 hours,-drain,-scrub and refill the hot tub-submit a water sample. Please follow the directions as indicated in the Pseudomonas information sheet, The information sheet will be sent with the report in an email. The hot tub shall remain closed until a satisfactory water result is received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The laboratory report indicated HPC at 57000 CFU/ml. Please super chlorinate the pool.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The laboratory report indicated Pseudomonas isolated. Please close the hot tub. Please backwash, super chlorinate for 4 -6 hours, drain,scrub the hot tub and submit a water sample. Please follow the directions as indicated in the Pseudomonas information sheet, The information sheet will be sent with the report in an email. The hot tub shall remain closed until a satisfactory water result is received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The laboratory report indicated HPC at 2980 CFU/ml. Please super chlorinate the pool.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The automatic chemical dispenser for the hot tub is not functioning properly, potentially due to a sensor issue. Please repair or replace automatic chemical dispenser. Please descale or replace the sensor.For descaling:-Contact the company which installed the sensor for a demonstration on how to descale the sensor. -Add the descaling of the sensor to the maintenance schedule. Maintenance staff indicated that there are plans to replace the system. Not observed during the August 29, 2023 inspection.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas Aeruginosa is indicated on the lab report. Please close the pool, scrub and super chlorinate the hot tub.Instructions on how to clean the hot tub will be sent with the report via email. ** The hot tub shall remain closed until a satisfactory lab result is received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC of 57000 CFU/ml is noted on the lab report.Please super chlorinate the hot tub.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The automatic chemical dispenser for the hot tub is not functioning properly, potentially due to a sensor issue. Please repair or replace automatic chemical dispenser. Please descale or replace the sensor.For descaling:-Contact the company which installed the sensor for a demonstration on how to descale the sensor. -Add the descaling of the sensor to the maintenance schedule. Maintenance staff indicated that there are plans to replace the system. Not observed during the August 29, 2023 inspection.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The following chemical perimeters are out of compliance:-pH= 6.65-FAC= 0.11-ORP=646 mv/LPlease raise the pH to 6.8-7.6 and free available chlorine to 2.0 ppm.The operator raised the pH to 6.98 and the FAC to 5.12 during the inspection.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity is noted at 11 ppm.Please ensure the alkalinity is maintained between 60 and 180 ppm. The pool operator raised the alkalinity during the inspection to 85 ppm.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The automatic chemical dispenser for the hot tub is not functioning properly, potentially due to a sensor issue. Please repair or replace automatic chemical dispenser. Please descale or replace the sensor.For descaling:-Contact the company which installed the sensor for a demonstration on how to descale the sensor. -Add the descaling of the sensor to the maintenance schedule. Maintenance staff indicated that there are plans to replace the system. Not observed during the August 29, 2023 inspection.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The pool testing chemicals are expired, indicating false readings for the pH, FAC, CC, and alkalinity. Please replace the chemicals and verify the expiry dates regularly. The pool operator replaced the chemicals during the inspection.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?