Hilton Garden Inn West Edmonton - Swimming Pool

17610 Stony Plain Road NW Edmonton AB T5S 1A2 · Aquatic Facility

13 inspections

  1. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The pool stairs on the left side of the mechanical room is broken at the edges. Please repair
  2. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on May 1, 2026, was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The pool stairs on the left side of the mechanical room is broken at the edges. Please repair
  3. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The pool stairs on the left side of the mechanical room is broken at the edges. Please repair
  4. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH was measured at greater than 7.6.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total Alkalinity was measured at greater than 180 ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The pool stairs on the left side of the mechanical room is broken at the edges. Please repair
  5. Monitoring Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Two inlet covers missing. One in the deep end and one in the shallow end. Replace.August 14 2025; Violation still outstanding
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The pool stairs on the left side of the mechanical room is broken at the edges. Please repair
  6. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Two inlet covers missing. One in the deep end and one in the shallow end. Replace.
  7. Risk Management Inspection

    0 infractions

  8. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the bacteriological water sample collected on 7 June 2024 was unsatisfactory. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  9. Risk Management Inspection

    0 infractions

  10. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Automated reading FCL was 0.08ppm, Controller was turned off and dechlor was added. It has been appeared that automated controller is over feeding chlorine.Operator already added chemicals in the pool to balance the chemistry to balance the water. Send daily water results daily to the undersigned.
  11. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Automated reading FCL was 0.08ppm, Controller was turned off and dechlor was added. It has been appeared that automated controller is over feeding chlorine.Operator already added chemicals in the pool to balance the chemistry to balance the water. Send daily water results daily to the undersigned.
  12. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Manual reading FCL 0.55ppm, while the automated reading FCL was 0.39ppm, both of which were below the acceptable range (at least 1.00ppm if no ORP readings is available).Operator began added chemicals in the pool to balance the chemistry during inspection onsite. Send water results after balancing water chemistry to the undersigned.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Feb 22; Total Alkalinity; 55ppm Feb 12; Total Alkalinity: 30ppm Ensure total alkalinity is maintained between 60-180ppm.
  13. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity: 30ppm Ensure total alkalinity is maintained between 60-180ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Discrepancies were noted in water chemistry automated controller readings and manual tests readings. Automated Controller: FCL: 2.74 VS manual test FCL 5.88.Have Ecolab onsite for service.2. Rust build up was noted in the flowmeter. The float was not visible to read flow rate.Clean the flow meter and maintain it in a clean and working condition.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Water testing is not being done on Sunday. Water chemistry must be tested daily to ensure the water safety.Make arrangements for water chemistry to be tested and ensure water safety over the weekend.