Holiday Inn Express & Suites - Edmonton SW Windermere - Swimming Pool
6125 Andrews Loop SW Edmonton AB T6W 3G9 · Aquatic Facility
Inspection summary
Holiday Inn Express & Suites - Edmonton SW Windermere - Swimming Pool has been inspected 10 times by Alberta Health Services (Environmental Public Health) since November 24, 2023. The most recent inspection, on July 2, 2026, found no infractions.
2 of 10 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 5 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality, Chemicals and toxic substances and Food temperature control.
Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 10 times across 8 separate inspections, most recently on June 22, 2026. For example:
Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded 5 times across 5 separate inspections, most recently on June 2, 2026. For example:
Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
Food temperature controlHigher risk
Inspectors check that anything that has to be kept at a set temperature, such as chilled or hot food, or equipment like sterilizers, stays in its safe range and that accurate thermometers are on hand. With food, temperature problems are one of the most common causes of food poisoning.
Recorded once on June 2, 2026. For example:
Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
10 inspections
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 18.74 gpm/sq ft based on a filtration area of 4.91 sq ft and flow rate about 92 gpm. Ensure that the rate of filtration is 15 gpm/sq ft or less. (To achieve the proper rate of filtration, the flow rate should not exceed 73 gpm). Updated on June 16, 2026:* Rate of filtration for the filtration system was 19.35 gpm/sq ft based on a filtration area of 4.91 sq ft and flow rate about 95 gpm. Ensure that the rate of filtration is 15 gpm/sq ft or less. (To achieve the proper rate of filtration, the flow rate should not exceed 73 gpm). Updated on June 22, 2026:* Rate of filtration for the filtration system was 16.29 gpm/sq ft based on a filtration area of 4.91 sq ft and flow rate about 80 gpm. Ensure that the rate of filtration is 15 gpm/sq ft or less.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 18.74 gpm/sq ft based on a filtration area of 4.91 sq ft and flow rate about 92 gpm. Ensure that the rate of filtration is 15 gpm/sq ft or less. (To achieve the proper rate of filtration, the flow rate should not exceed 73 gpm). Updated on June 16, 2026:* Rate of filtration for the filtration system was 19.35 gpm/sq ft based on a filtration area of 4.91 sq ft and flow rate about 95 gpm. Ensure that the rate of filtration is 15 gpm/sq ft or less. (To achieve the proper rate of filtration, the flow rate should not exceed 73 gpm).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was 50 ppm. Ensure that the total alkalinity is maintained between 60 and 180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 18.74 gpm/sq ft based on a filtration area of 4.91 sq ft and flow rate about 92 gpm. Ensure that the rate of filtration is 15 gpm/sq ft or less. (To achieve the proper rate of filtration, the flow rate should not exceed 73 gpm).
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- One weir was missing in a skimmer. Please replace the missing weir.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 19.3 gpm/sq ft (too fast) based on a filtration area of 4.91 sq ft. Ensure that the flow rate is around 73 gpm for required rate of filtration. Updated on February 11, 2025:Rate of filtration for the filtration system was 20.37 gpm/sq ft based on a filtration area of 4.91 sq ft and flow rate about 100 gpm. Ensure that the rate of filtration is 15 gpm/sq ft or less.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine residual was 1.75 ppm. Ensure that the combined chlorine is maintained at the lowest level possible (and below 1 ppm).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 19.3 gpm/sq ft (too fast) based on a filtration area of 4.91 sq ft. Ensure that the flow rate is around 73 gpm for required rate of filtration.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 24EN-178E01134 submitted on June 26, 2024, was unsatisfactory: HPC 290.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine residual was 1.75 ppm. Ensure that the combined chlorine is maintained at the lowest level possible (and below 1 ppm).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 19.3 gpm/sq ft (too fast) based on a filtration area of 4.91 sq ft. Ensure that the flow rate is around 73 gpm for required rate of filtration.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine residual was 1.75 ppm. Ensure that the combined chlorine is maintained at the lowest level possible (and below 1 ppm).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 19.3 gpm/sq ft (too fast) based on a filtration area of 4.91 sq ft. Ensure that the flow rate is around 73 gpm for required rate of filtration.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample WE-23-0125681 submitted on November 22, 2023, was unsatisfactory: HPC 270.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine residual was 1.75 ppm. Ensure that the combined chlorine is maintained at the lowest level possible (and below 1 ppm).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 19.3 gpm/sq ft (too fast) based on a filtration area of 4.91 sq ft. Ensure that the flow rate is around 73 gpm for required rate of filtration.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
Nearby inspected facilities
- Holiday Inn Express & Suites - Edmonton SW Windermere - Common Area
6125 Andrews Loop SW Edmonton AB T6W 3G9
5 inspections
- Holiday Inn Express & Suites - Restaurant
6125 Andrews Loop SW Edmonton AB T6W 3G9
6 inspections
- Holiday Inn Express & Suites - Edmonton SW Windermere - Whirlpool
6125 Andrews Loop SW Edmonton AB T6W 3G9
10 inspections
- Golf 360
6031 Andrews Way SW Edmonton AB T6W 3S9
3 inspections
- Maple Pharmacy
111 - 6055 Andrews Way SW Edmonton AB T6W 3S9
1 inspection
- Miss Oxygen
3522 Allan Drive SW Edmonton AB T6W 3G9
3 inspections
- E Cosmetic / Evergreen Cosmetic
3522 Allan Drive SW Edmonton AB T6W 3G9
4 inspections
- Lotus Blossom Wellness / Thrive Chiropractic and Wellness Centre
101 - 6050 Andrews Way SW Edmonton AB T6W 3S9
2 inspections