Skip to content
Loading map…

Holiday Inn & Suites Grande Prairie - Whirlpool

9816 107 Street Grande Prairie AB T8V 1L4 · Aquatic Facility

9 inspections

  1. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 8/31. The bacterial water sample submitted on August 26th was unsatisfactory. - TC: Absent.- HPC: 200 CFU/mL**- Pseudomonas aeruginosa: not isolatedEnsure the treatment system is operating properly (i.e., chlorine levels are high enough), treat the whirlpool as necessary, and resample.
  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • A microbiological water sample was collected and submitted to the regional health authority on June 17, 2026. The results were as follows:Pseudomonas aeruginosa - ISOLATEDDrain, clean, refill and shock chlorinate the hot tub. Once water chemistry is balanced, submit another water sample this week.This pool must remain closed until such time that a satisfactory whirlpool water sample result is achieved.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • A microbiological water sample was collected and submitted to the regional health authority on June 17, 2026. The results were as follows:HPC: >57,000 CFU/mLEnsure HPC is less than 100 CFU/mL.Drain, clean, refill and shock chlorinate the hot tub. Once water chemistry is balanced, submit another water sample this week.
  4. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on April 28, 2026.HPC: 630 CFU/mLEnsure HPC is less than 100 CFU/mL.Drain, clean, refill and shock chlorinate the hot tub. Once water chemistry is balanced, submit another water sample this week.
  5. Monitoring Inspection

    0 infractions

  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC: 800 CFU/mLEnsure HPC is less than 100 CFU/mL.Drain, clean, refill and shock chlorinate the hot tub. Once water chemistry is balanced, submit another water sample this week.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free available chlorine (FAC) is at 1.53 ppm. FAC must be maintained 2.0 ppm in a public swimming pool with an operating water temperature of greater than 30 degrees Celsius
  8. Monitoring Inspection

    1 infraction

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free available chlorine (FAC) is at 1.53 ppm. FAC must be maintained 2.0 ppm in a public swimming pool with an operating water temperature of greater than 30 degrees Celsius
  9. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC Count 950cfu/mlRequired to resample as soon as possible. Ensure all chemical parameters are maintained in acceptable range.