Holiday Inn & Suites West Edmonton - Swimming Pool

11330 170 Street NW Edmonton AB T5S 2X1 · Aquatic Facility

11 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate was observed to be at 53 GPM.Filter area: 3.1 sq ftFiltration rate: 17.1 gpm/sq ft Corrective Action- Decrease the flow rate to ensure the filtration rate does not exceed 15 GPM/sq ft.- Note, this specific system can operate at 46-47 GPM to maintain the required filtration rate (and recirculation rate).
  3. Risk Management Inspection

    0 infractions

  4. Risk Management Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • During the inspection it was found that the free chlorine was at 0.31ppm. Please raise and maintain the free chlorine levles above 1ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was tested to be 1.57 ppm at the time of inspection, this was higher than the tested free chlorine levels of 0.31ppm.Please ensure that the combined chlorine levels are maintained as low as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • During the inspection the filtration rate was observed to be 17.4 GPM/sq ft. The flow rate of the pool was raised from 50 Gallons Per Minute (GPM) that was previously cited as a violation for having a filtration rate of 16.1 GPM/sq ft to flow rate of 54 GPM equaling a filtration rate of 17.4 GPM/sq ft.Having a filtration rate that is too high may cause tunneling in the sand bed of the sand filters. When tunneling occurs the water is not being filtered enough to be properly cleaned of all debris as intended by the manufactures of the sand filter. The flow rate of the water needs to be lowered in order to comply with the legislation. Lowering the flow rate to 45GPM will give a turnover of 4 hours and a filtration rate of 14.5GPM/sq ft rendering both these values in compliance.Please ensure the filtration rate for the pool is no more than 15 GPM/sq ft at all times.
  5. Monitoring Inspection

    4 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1.The total alkalinity of the swimming pool was tested to be at 54 ppm during the time of the inspection. Please ensure that the total alkalinity is maintained between 60-180ppm.2. The combined chlorine was tested to be 1.54 ppm at the time of inspection, this was higher than the tested free chlorine levels of 1.37.Please ensure that the combined chlorine levels are maintained as low as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • During the inspection the filtration rate was observed to be 16.1 GPM/sq ft. Please ensure the filtration rate is no more than 12.5 GPM/sq ft at all times.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • 1. A tile was missing from the edge of the swimming pool on the side of the emergency exit door near the deep end of the pool. Please ensure that all finishes are maintained in good repair at all times. 2. Some tissue debris was visible at the bottom of the swimming pool at the time of inspection. Please ensure that the pool in maintained in a clean condition at all times.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Inconsistencies in daily record keeping for the water quality tests was observed during the inspection. Please ensure that the daily testing log sheet is filled out for every day of operation.
  6. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floating weirs were missing from the skimmers.Install floating weirs or round weirs.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A few tiles were missing from the edge of the pool. Repair
  7. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate: 17.7gpm/sq ft
  8. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 1-Manual reading of PH was greater than 6.7.2- The automated controller reading (7.4) did not match the manual chemistry reading (7.73). Troubleshoot and make the necessary modifications. The probes may need to be cleaned, calibrated or replaced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate: 17.7gpm/sq ft
  9. Risk Management Inspection

    0 infractions

  10. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Information provided over the phone that main drain covers had been changed in Dec 2023. Update Anti-entrapment plan and resubmit it to the undersigned.
  11. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result submitted on 29-12-2023 Accession #WE-23-0137458 was unsatisfactory. HPC >57000CFU/ml.Take all necessary action to ensure microbiologically safe water. Submit a new microbiological watersample at your earliest convenience once the water chemistry is balanced.