  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample (26ES-159E00032) collected on June 8th, 2026, came back unsatisfactory as the HPC was elevated to 710CFU/mL. The maximum acceptable concentration is 100CFU/mL. Please resample as soon as possible.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample (26ES-155E00220) collected on June 3rd, 2026, @ 9:15 was rejected by the lab as it was received more than 24 hours after collection (received date/time: June 4th,2026 @ 13:53). Please submit a new sample as soon as possible.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • All of the water chemistry testing reagents were expired. Please replace all expired reagents to ensure testing is accurate.
  4. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • All of the water chemistry testing reagents were expired. Please replace all expired reagents to ensure testing is accurate.
  5. Monitoring Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A large amount of debris was observed on the bottom of the pool. Please vacuum the pool basin.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • All of the water chemistry testing reagents were expired. Please replace all expired reagents to ensure testing is accurate.
  6. Monitoring Inspection

    0 infractions

  7. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken Aug 22, 2024 - HPC 110 CFU/mL.-Resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • pH test from inspector's kit (6.99) and automated reader (6.5) are very far apart.-Ensure that automated reader is properly calibrated
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1) Operator not recording routine automatic shutoff system testing.-Record regular testing of automatic shutoff system2) Clarity checks not being recorded.-Record daily clarity checks-
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan has not been updated (shows a cover that expired May 2023). Operator had evidence that new one was purchased in 2023. -Update the plan with the drain cover certificate and installation/expiry date
  8. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken May 22, 2024 not processed (submitted >24 hours after sample taken).-Take in a new sample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • pH test from inspector's kit (6.99) and automated reader (6.5) are very far apart.-Ensure that automated reader is properly calibrated
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1) Operator not recording routine automatic shutoff system testing.-Record regular testing of automatic shutoff system2) Clarity checks not being recorded.-Record daily clarity checks-
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan has not been updated (shows a cover that expired May 2023). Operator had evidence that new one was purchased in 2023. -Update the plan with the drain cover certificate and installation/expiry date
  9. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • pH test from inspector's kit (6.99) and automated reader (6.5) are very far apart.-Ensure that automated reader is properly calibrated
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1) Operator not recording routine automatic shutoff system testing.-Record regular testing of automatic shutoff system2) Clarity checks not being recorded.-Record daily clarity checks-
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan has not been updated (shows a cover that expired May 2023). Operator had evidence that new one was purchased in 2023. -Update the plan with the drain cover certificate and installation/expiry date
  10. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 1000 CFU/mL-Re-sample
  11. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample taken Aug 1 had total coliforms present.-Treat and re-sample
  12. Risk Management Inspection

    0 infractions