Super 8 by Wyndham Canmore - Whirlpool

1506 Bow Valley Trail Canmore AB T1W 1N5 · Aquatic Facility

8 inspections

  1. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • *Updated anti-entrapment plan sent but several errors on the plan. To redo and resend. Need one for both the recirculation pump submerged suction outlets and for the hydro-jet submerged suction outlets. New plans to be completed asap.
  2. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was below the minimum flow rate of 180GPM, flow meter was reading 171.6 GPM. The Turnover period calculated was 21mins, it was higher than the maximum of 20mins. Filtration rate was 6.57 GPM/sqft.Requirement:- Ensure flow rate is above 180GPM for maximum turn over period and below 326.5GPM for the filters.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Updated anti-entrapment plan sent but several errors on the plan. To redo and resend.
  3. Risk Management Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample taken on January 26, 2026 had Pseudomonas present.Close whirlpool until a Pseudomonas disinfection is done. Once completed, whirlpool may reopen. Ensure a new water sample is submitted.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was below the minimum flow rate of 180GPM, flow meter was reading 171.6 GPM. The Turnover period calculated was 21mins, it was higher than the maximum of 20mins. Filtration rate was 6.57 GPM/sqft.Requirement:- Ensure flow rate is above 180GPM for maximum turn over period and below 326.5GPM for the filters.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Updated anti-entrapment plan sent but several errors on the plan. To redo and resend.
  4. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample taken on January 26, 2026 had Pseudomonas present.Close whirlpool until a Pseudomonas disinfection is done. Once completed, whirlpool may reopen. Ensure a new water sample is submitted.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was below the minimum flow rate of 180GPM, flow meter was reading 171.6 GPM. The Turnover period calculated was 21mins, it was higher than the maximum of 20mins. Filtration rate was 6.57 GPM/sqft.Requirement:- Ensure flow rate is above 180GPM for maximum turn over period and below 326.5GPM for the filters.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The recirculation suction outlet covers has expired.RequirementReplace all expired suction outlet covers.
  5. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • No water samples were submitted the week of Dec. 22nd or the week of Dec. 29th, 2025. Water samples are to be submitted weekly when the whirlpool is in operation.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was below the minimum flow rate of 180GPM, flow meter was reading 171.6 GPM. The Turnover period calculated was 21mins, it was higher than the maximum of 20mins. Filtration rate was 6.57 GPM/sqft.Requirement:- Ensure flow rate is above 180GPM for maximum turn over period and below 326.5GPM for the filters.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The recirculation suction outlet covers has expired.RequirementReplace all expired suction outlet covers.
  6. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate was below the minimum flow rate of 180GPM, flow meter was reading 171.6 GPM. The Turnover period calculated was 21mins, it was higher than the maximum of 20mins. Filtration rate was 6.57 GPM/sqft.Requirement:- Ensure flow rate is above 180GPM for maximum turn over period and below 326.5GPM for the filters.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The recirculation suction outlet covers has expired.RequirementReplace all expired suction outlet covers.
  7. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken on May 8/25 had total coliforms isolated. Treat water to remove contamination. Resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Valve for main drain was fully open. Are to maximize the flow through the skimmers, not the main drain. Do not keep valve for main drain fully open.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meters for the filters were not installed correctly (can't be installed on an angle) so the flow through each filter can't be determined. Please properly install flow meters so that the flow through each filter can be determined.
  8. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Valve for main drain was fully open. Are to maximize the flow through the skimmers, not the main drain. Do not keep valve for main drain fully open.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The flow meters for the filters were not installed correctly (can't be installed on an angle) so the flow through each filter can't be determined. Please properly install flow meters so that the flow through each filter can be determined.