Super 8 by Wyndham Edmonton South - Swimming Pool

3610 Gateway Boulevard NW Edmonton AB T6J 7H8 · Aquatic Facility

7 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floor inlet cover by the stairs was missing. Manager stated that the cover has been ordered and they are awaiting receipt. Confirm with the undersigned once the return inlet cover is installed.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Scum line was noted on the tile above the water line along the preimeter of the pool basin. Remove the scum line noted in the pool. Ensure staff are cleaning more regularly to prevent a buildup.
  3. Risk Management Inspection

    0 infractions

  4. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • ORP (actual) was higher than the set point however free chlorine was noted slightly below 1ppm. Contact pool service provider to discuss possible adjustment to the controller to ensure consistent chlorine concentration.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A scum line was observed on the sidewalls of the pool basin.Clean the pool wall to remove scum line, make sure that pool basin is maintained in clean and sanitary condition.
  5. Risk Management Inspection

    0 infractions

  6. Monitoring Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • A new slide pump was noted since last inspection. Ensure that the anti-entrapment compliance plan is reviewed and updated to reflect the new pumps installed in the system.
  7. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on [Date] was unsatisfactory: HPC 1270 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.