Best Western Port O'Call - Kiddie Pool

1935 McKnight Boulevard NE Calgary AB T2E 6V4 · Aquatic Facility

9 inspections

  1. Demand Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total Alkalinity was measured at 192 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured at 2.09 ppm. Please maintain the combined chlorine to as low as possible, ideally below 0.5 ppm.**OUTSTANDING (2025-03-12). The combined chlorine was measured at 2.02 ppm.
  2. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured at 2.09 ppm. Please maintain the combined chlorine to as low as possible, ideally below 0.5 ppm.**OUTSTANDING (2025-03-12). The combined chlorine was measured at 2.02 ppm.
  3. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on January 9, 2025, was unsatisfactory with the presence of Pseudomonas aeruginosa.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured at 2.09 ppm. Please maintain the combined chlorine to as low as possible, ideally below 0.5 ppm.**OUTSTANDING (2025-03-12). The combined chlorine was measured at 2.02 ppm.
  4. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured at 2.09 ppm. Please maintain the combined chlorine to as low as possible, ideally below 0.5 ppm.**OUTSTANDING (2025-03-12). The combined chlorine was measured at 2.02 ppm.
  5. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on May 9, 2025, was not tested as the sample was received during the weekend/holiday without approval.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured at 2.09 ppm. Please maintain the combined chlorine to as low as possible, ideally below 0.5 ppm.**OUTSTANDING (2025-03-12). The combined chlorine was measured at 2.02 ppm.
  6. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured at 2.09 ppm. Please maintain the combined chlorine to as low as possible, ideally below 0.5 ppm.**OUTSTANDING (2025-03-12). The combined chlorine was measured at 2.02 ppm.
  7. Demand Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was measured to be 47 ppm. Maintain the total alkalinity between 60-180 ppm.**OUTSTANDING (2025-02-14). The total alkalinity was measured to be 49 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured at 2.09 ppm. Please maintain the combined chlorine to as low as possible, ideally below 0.5 ppm.
  8. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine level was measured to be 1.86 ppm.REQUIREMENT: Maintain the free chlorine level at a minimum of 2.00 ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was measured to be 47 ppm.REQUIREMENT: Maintain the total alkalinity between 60-180 ppm.
  9. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate is too low; the minimum turnover period will not be achieved with the current flow of the pool.REQUIREMENT: Maintain the flow between 29 USGPM and 73 USGPM
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)