Best Western Port O'Call - Main Slide Pool
1935 McKnight Boulevard NE Calgary AB T2E 6V4 · Aquatic Facility
Inspection summary
Best Western Port O'Call - Main Slide Pool has been inspected 23 times by Alberta Health Services (Environmental Public Health) since October 20, 2023. The most recent inspection, on October 6, 2026, recorded 3 infractions.
None of the 23 inspections on record were free of infractions. In the past 12 months there were 5 inspections with 15 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.
The number of infractions per inspection has stayed roughly the same over time.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 47 times across 23 separate inspections, most recently on October 6, 2026. For example:
Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded 12 times across 9 separate inspections, most recently on October 6, 2026. For example:
Is the chemical quality of the water in this pool satisfactory (Critical)?
Food safety training and certificationLower risk
Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.
Recorded 10 times across 10 separate inspections, most recently on August 22, 2024. For example:
Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
23 inspections
- Risk Management Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH was measured at 7.88.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding**The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Not observed**The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on September 4, 2026, was not tested because there was no identification number on the bottle.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH was measured at 7.88.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding**The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Not observed**The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH was measured at 7.88.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding**The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Not observed**The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding**The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Not observed**The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on 30/01/2026, tested positive for Total Coliforms.Treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding**The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Not observed**The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding**The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Not observed**The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on May 30, 2025, had Total Coliforms present in the sample.**Please begin treatment for the swimming pool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on May 23, 2025, had Total Coliforms present in the sample.**Please begin treatment for the swimming pool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding**The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**ONGOING CONCERN/VIOLATION****OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Not observed**The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**ONGOING CONCERN/VIOLATION****OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The Free Available Chlorine (FAC) was measured to be 0.23 ppm. Please maintain the FAC concentration to be at least 1.0 ppm at all times.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH of the swimming pool was measured to be 7.87. Please ensure to maintain the pH of the swimming pool within the required range, between 6.8 and 7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**ONGOING CONCERN/VIOLATION****OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine concentration was at least or more than 1.84 ppm. Please decrease the combined chlorine concentration to as low as possible, ideally below 0.5 ppm.**OUTSTANDING (2025-03-12). The combined chlorine was measured to be at least 1.18 ppm based on the limitation of the pool testing equipment (can only read a maximum total chlorine concentration of 6.0 ppm; free available chlorine was measured at 4.82 ppm). Please decreased the combined chlorine to as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**ONGOING CONCERN/VIOLATION****OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine concentration was at least or more than 1.84 ppm. Please decrease the combined chlorine concentration to as low as possible, ideally below 0.5 ppm.**OUTSTANDING (2025-03-12). The combined chlorine was measured to be at least 1.18 ppm based on the limitation of the pool testing equipment (can only read a maximum total chlorine concentration of 6.0 ppm; free available chlorine was measured at 4.82 ppm). Please decreased the combined chlorine to as low as possible.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was measured at 44 ppm. The operator added 11.5 kg of sodium bicarbonate and raised the total alkalinity to 75 ppm. Please ensure to maintain the total alkalinity to at least 60 ppm at all times.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006. Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.**ONGOING CONCERN/VIOLATION****OUTSTANDING (2025-03-12). The pool's flow rate was too low and not within the required range. Please ensure to maintain the flow rate to at least 112 GPM and not exceeding 147 GPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated reading for pH (7.4) was not consistent with the manual test result (7.04). Please calibrate the probes for the automated controller.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine concentration was at least or more than 1.84 ppm. Please decrease the combined chlorine concentration to as low as possible, ideally below 0.5 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 27000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 112 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on May 17, 2024, had an HPC Count of 110 CFU/mL in the sample.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 01 2023 had HPC detected at 540 CFU/mL.The water sample collected on November 08 2023 had HPC detected at 1480 CFU/mL.The water sample collected on November 14 2023 had HPC detected at 1650 CFU/mL.REQUIREMENT: Close the pool and treat the water chemistry for the main slide pool and balance as needed. Send in a re-sample when treatment is complete and the water chemistry appears satisfactory.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 01 2023 had HPC detected at 540 CFU/mL.The water sample collected on November 08 2023 had HPC detected at 1480 CFU/mL.REQUIREMENT: Review and treat the water chemistry for the main slide pool and balance as needed. Send in a re-sample when treatment is complete and the water chemistry appears satisfactory.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 01 2023 had HPC detected at 540 CFU/mL.REQUIREMENT: Review the water chemistry for the main slide pool and balance as needed. Send in a re-sample when the water chemistry appears satisfactory.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 01 2023 had HPC detected at 540 CFU/mL.REQUIREMENT: Review the water chemistry for the main slide pool and balance as needed. Send in a re-sample when the water chemistry appears satisfactory.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Last inspection, it was noted that: "the total alkalinity was measured to be OR (i.e. greater than 200 ppm). The pH of the pool appears to be locked."This inspection, the total alkalinity was measured to be 15 ppm.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- There appeared to be an air blockage in the chlorine line for the swimming pool. As the pump attempted to push hypochlorite into the basin, air bubbles were being introduced into the line. The floating ball indicator that shows flow in the line stopped moving. Maintenance staff onsite attempted to clear the line, with partial success since the line was re-blocking itself with air.REQUIREMENT: Immediately repair the feeder system and ensure the feeder system can continuously added hypochlorite into the pool when needed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 01 2023 had HPC detected at 540 CFU/mL.REQUIREMENT: Review the water chemistry for the main slide pool and balance as needed. Send in a re-sample when the water chemistry appears satisfactory.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- 1) The pH was measured to be 7.98.REQUIREMENT: Maintain the pH between 6.8 and 7.62) The FCL was measured to be 0.34 ppm.REQUIREMENT: Increase the FCL above 1.0 ppm in a pool less than 30C.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was measured to be OR (i.e. greater than 200 ppm). The pH of the pool appears to be locked.REQUIREMENT: Maintain the total alkalinity between 60 - 180 ppm. Partially drain the pool or add acid to lower the total alkalinity.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Ongoing Concern** The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 01 2023 had HPC detected at 540 CFU/mL.REQUIREMENT: Review the water chemistry for the main slide pool and balance as needed. Send in a re-sample when the water chemistry appears satisfactory.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on October 18, 2023 had HPC detected at 2680 CFU/mL.REQUIREMENT: Review the water chemistry for the main slide pool and balance as needed. Send in a re-sample when the water chemistry appears satisfactory.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The main pool's flow rate was too low, based on an approximately 30000-gallon pool built after November 2006.REQUIREMENT: Increase the flow rate so it is higher than 125 USGPM and does not exceed 147 USGPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The Anti-Entrapment plans have not been properly completed.REQUIREMENT: Complete the anti-entrapment plans as soon as possible as required on the current work order (common area report)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
Nearby inspected facilities
- Best Western Port O'Call - South Whirlpool
1935 McKnight Boulevard NE Calgary AB T2E 6V4
18 inspections
- Best Western Port O'Call - Lower Swimming Pool
1935 McKnight Boulevard NE Calgary AB T2E 6V4
30 inspections
- Best Western Port O'Call - Kiddie Pool
1935 McKnight Boulevard NE Calgary AB T2E 6V4
9 inspections
- Best Western Port O'Call - Lower Whirlpool
1935 McKnight Boulevard NE Calgary AB T2E 6V4
19 inspections
- Best Western Port O'Call - North Whirlpool
1935 McKnight Boulevard NE Calgary AB T2E 6V4
13 inspections
- Best Western Port O'Call - Common
1935 McKnight Boulevard NE Calgary AB T2E 6V4
6 inspections
- Best Western Port O'Call - Food
1935 McKnight Boulevard NE Calgary AB T2E 6V4
6 inspections
- Calgary Canadian Irish Athletic Club
4334 18 Street NE Calgary AB T2E 8P4
1 inspection