Best Western Rocky Mountain House Inn & Suites - Pool

4407 41 Avenue Rocky Mountain House AB T4T 1A5 · Aquatic Facility

19 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
      • The anti-entrapment plan submitted demonstrated that total flow at the main drains can exceed the ratings for the drain covers. Though this demonstration does not reflect normal operating conditions, it proves that there is a possible means for this total flow to exceed the drain covers and create an entrapment hazard. The method identified to ensure the conditions do not happen is not sufficient.*** Please ensure that adequate correction action is installed as was discussed. ***
  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample result for sample taken 2Dec2025: total coliforms = absent heterotrophic plate count = 110 cfu/mLPool is being shocked. Resampling to occur next week.
  5. Risk Management Inspection

    0 infractions

  6. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Elevate HPC noted as part of last sampling episode.*** Please resample this week, indicating that the sample is a "RE-SAMPLE". ***
  7. Risk Management Inspection

    0 infractions

  8. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Floating weirs were missing from skimmers. The operator confirmed weirs were removed that day due to issues with patrons pulling them out, and indicated that they would be re-installed that day.Please ensure floating weirs are present for the effective debris removal from the surface.
  9. Risk Management Inspection

    1 infraction

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Anti-entrapment plan provided at this inspection shows the main drain covers were due to be replaced in Feb. 2024. Covers that are past their manufacturer's replacement date are not safe for use and could pose an entrapment hazard. Please ensure covers are replaced.
  10. Monitoring Inspection

    2 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The pool enclosure area has no working phone at this time. Please ensure a working phone is present so contact with emergency services can be done quickly in the event of an emergency
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • : Records being kept did not include the water temperature of the basins and amounts of chemicals being added to the pools. Testing of the phone daily should also be recorded as part of the safety plan, so corrective action can be taken immediately if found not to be working.Section 5.1(d) of the Pool Standards requires the temperature of the pool basin to be recorded and section 5.1(h) requires the quantity of chemicals used to be recorded.Please add these three items to the daily checklist
  11. Risk Management Inspection

    0 infractions

  12. Monitoring Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unacceptable sample results for sample taken 3Sept2024; Heterotrophic Plate Count of 3450 cfu/mL.*** Please immediate close the pool and shock chlorinate. Resample next week. ***
  13. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Unacceptable sample results for sample taken 21Aug2024; Heterotrophic Plate Count of 3030 cfu/mL.*** Please immediate close the pool and shock chlorinate. Resample on Wednesday 28Aug2024. ***
  14. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Resample results were received for sample taken on 16Apr2024. Sample results show heterotrophic plate count at 120 cfu/mL.*** Please immediately close the pool and shock chlorinate. Resample on Tuesday 23Apr2024. ***
  15. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample results were received for sample taken on 10Apr24. Sample results show heterotrophic plate count at 250 cfu/mL.*** Please immediately close the pool and shock chlorinate. Resample on Tuesday 16Apr24. ***
  16. Monitoring Inspection

    0 infractions

  17. Risk Management Inspection

    0 infractions

  18. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample results were received for sample taken on 27Dec23. Sample results show the presence of Total coliform bacteria.*** Please immediately close the pool and shock chlorinate. Resample next week on Tuesday. ***
  19. Initial Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The floating weirs in the skimming system were missing. The floating weirs allow the dirtiest portion of the water at the surface to enter into the filtration system. Please ensure that the floating weirs are present to ensure adequate cleaning of the water. The operator located the missing components and installed them during the inspection.