Delta Hotels by Marriott Calgary Downtown - Swimming Pool
209 4 Avenue SE Calgary AB T2G 0C6 · Aquatic Facility
11 inspections
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The operator stated the main drain covers have all been replaced. However, the anti-entrapment plan had not been updated to reflect this change. Please update the anti-entrapment plan to reflect the cover change and provide supporting documentation.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Monitoring Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was 1.3ppm. Please keep the combined chlorine as low as possible (recommend to not exceed 1.0ppm) to prevent skin and eye irritation for bathers.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- June 1st, 2026: unable to assess as flow meter was broken. Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- (Outstanding violation)The flow meter of the swimming pool was broken.-Repair/replace/fix the flow meter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The operator stated the main drain covers have all been replaced. However, the anti-entrapment plan had not been updated to reflect this change. Please update the anti-entrapment plan to reflect the cover change and provide supporting documentation.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1)The flow meter of the swimming pool was broken.-Repair/replace/fix the flow meter.2) The automated chemical feeding and monitoring readings were not consistent with the manual readings. Scaling was observed on the automate probes.-Clean/repair/replace the automated probes and ensure that the automated readings are consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample (26ES-127E00331) collected on May 7th, 2026, came back unsatisfactory as total coliforms were present in the sample. Please treat the pool, rebalance, and resample as soon as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1)The flow meter of the swimming pool was broken.-Repair/replace/fix the flow meter.2) The automated chemical feeding and monitoring readings were not consistent with the manual readings. Scaling was observed on the automate probes.-Clean/repair/replace the automated probes and ensure that the automated readings are consistent with the manual readings.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1)The flow meter of the swimming pool was broken.-Repair/replace/fix the flow meter.2) The automated chemical feeding and monitoring readings were not consistent with the manual readings. Scaling was observed on the automate probes.-Clean/repair/replace the automated probes and ensure that the automated readings are consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-003E00002) submitted January 3, 2026 was not processed as it was submitted during a weekend without approval.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1)The flow meter of the swimming pool was broken.-Repair/replace/fix the flow meter.2) The automated chemical feeding and monitoring readings were not consistent with the manual readings. Scaling was observed on the automate probes.-Clean/repair/replace the automated probes and ensure that the automated readings are consistent with the manual readings.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1)The flow meter of the swimming pool was broken.-Repair/replace/fix the flow meter.2) The automated chemical feeding and monitoring readings were not consistent with the manual readings. Scaling was observed on the automate probes.-Clean/repair/replace the automated probes and ensure that the automated readings are consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (25ES-309E00424) collected on November 5th, 2025, was rejected by the lab as the time of collection was not recorded on the requisition form. Please resample the pool as soon as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1)The flow meter of the swimming pool was broken.-Repair/replace/fix the flow meter.2) The automated chemical feeding and monitoring readings were not consistent with the manual readings. Scaling was observed on the automate probes.-Clean/repair/replace the automated probes and ensure that the automated readings are consistent with the manual readings.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1)The flow meter of the swimming pool was broken.-Repair/replace/fix the flow meter.2) The automated chemical feeding and monitoring readings were not consistent with the manual readings. Scaling was observed on the automate probes.-Clean/repair/replace the automated probes and ensure that the automated readings are consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmer by door had no skimming mechanism.-Operator added a weir to the skimmer
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds manufacturer's instructions of 74 GPM through the filter.-Lower the filtration rate and follow the manufacturer's specification for the high rate sand filter
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main drain was barely visible due to extreme cloudiness of water. Pool operator had correctly closed the basin to public use prior to inspector's visit.-Improve the clarity so that the bottom of the basin is clearly visible, before reopening
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **Not reviewed on this visit**REPEAT VIOLATION: - Written policies and plans were updated, but were still incomplete. COMPLETE THE FOLLOWING: - Complete the written policies and plans in accordance with sections 10 to 13 of the Pool Standards.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **Not reviewed on this visit**VIOLATION: - The pool rules were incomplete. COMPLETE THE FOLLOWING:- Update the posted pool rules.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?