Douglas Fir Resort - Waterslide Outdoor Whirlpool
525 Tunnel Mountain Road Banff AB T1L 1B2 · Aquatic Facility
9 inspections
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Repeat Violation*Accurate flow was not able to be assessed; flow meters were broken; floats appeared to be stuck.- Repair or replace the flow meters, ensure the system is meeting turnover and filtration requirements.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- One of the lights was out of its socket. - Please repair the light, ensure the basin is maintained in good condition.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Monday August 18th, 2025, had Total Coliforms present.- Operators were informed to treat and re-sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday August 18th, 2025, had an HPC of 57,000 CFU/ml. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Repeat Violation*Flow was not able to be assessed; flow meters were broken (floats stuck). - Repair or replace the flow meters, ensure the system is meeting turnover and filtration requirements.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Monday August 18th, 2025, had Total Coliforms present.- Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Repeat Violation*Flow was not able to be assessed; flow meters were broken (floats stuck). - Repair or replace the flow meters, ensure the system is meeting turnover and filtration requirements.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Repeat Violation*Flow was not able to be assessed; flow meters were broken (floats stuck). - Repair or replace the flow meters, ensure the system is meeting turnover and filtration requirements.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Thursday October 3rd, 2024, has Pseudomonas isolated. - Operators were instructed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow was not able to be assessed; flow meters were broken (floats stuck). - Repair or replace the flow meters, ensure the system is meeting turnover and filtration requirements.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Monday June 10th, 2024, had an HPC of 150 cfu/ml. - Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow was not able to be assessed; flow meters were broken (floats stuck). - Repair or replace the flow meters, ensure the system is meeting turnover and filtration requirements.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow was not able to be assessed; flow meters were broken (floats stuck). - Repair or replace the flow meters, ensure the system is meeting turnover and filtration requirements.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity was high (over 200ppm). - Ensure alkalinity is maintained between 60-180ppm range.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Water leak noted from heat exchange loop. - Repair leak.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample not processed (October 10, 2023). No access number on the bottle. Can submit a re-sample on Thursday.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Chlorine was high at time of inspection (possibly due to sodium bicarbonate addition). Ensure controller is able to respond to chemical balance and measure all parameters prior to letting the public into the pool. You may need to add sodium bicarbonate in smaller amounts through-out the day or temporarily turn off controllers when there is a chemical addition.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- 1. Significant amount of sand was noted in the pool basin following backwash (ensure sand is not as a result of broken laterals). If only noted following backwash it is likely due to water pressure for backwash.2. A couple of flow meters had sand grains in the meter column (including cumulative flow) and significant scale on the top. Ensure these are cleaned so an accurate flow measurement can be read.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Water leak noted from heat exchange loop. Repair leak.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?