Fairfield Inn & Suites - Swimming Pool

581 Griesbach Parade NW Edmonton AB T5E 6W1 · Aquatic Facility

29 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on 12/11/2025 was unsatisfactory: HPC 230 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  3. Demand Inspection

    0 infractions

  4. Risk Management Inspection

    0 infractions

  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on 24/06/2025 [ID#: 25EN-175E00794] was unsatisfactory. HPC 150 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on 10/06/2025 [ID#: 25-EN-161E00804] was unsatisfactory: HPC 230 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  8. Risk Management Inspection

    0 infractions

  9. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on 24/03/2025 [ID: 25EN-084E00362] was unsatisfactory: HPC 790 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  10. Risk Management Inspection

    0 infractions

  11. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample collected on 2025-01-30 [ID#: 25EN-030E00536] was unsatisfactory: HPC 15 900 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  12. Risk Management Inspection

    0 infractions

  13. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on November 12, 2024, was unsatisfactory: HPC 150 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  14. Risk Management Inspection

    0 infractions

  15. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample results collected on 2024-09-24 [ID #: 24EN-268E00903] was unsatisfactory: HPC: 360 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample results collected on 17/09/2024 [ID #: 24EN-261E00801] was unsatisfactory: HPC 280 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  16. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample results collected on 17/09/2024 [ID #: 24EN-261E00801] was unsatisfactory: HPC 280 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  17. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Water levels were increased at time of inspection to ensure adequate skimming action.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Floating skimmer baskets had a build-up of scum which was cleaned at the time of inspection.
  18. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  19. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on 23/07/2024 [ID #: 24EN-205E00805] was unsatisfactory: HPC 130 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  20. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  21. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on 04/06/2024 [ID #: 24EN-156E01025] was unsatisfactory: HPC 120 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  22. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  23. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result submitted on 2024-02-27 [Accession #: WE-24-0019830] was unsatisfactory: HPC 240 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced..
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  24. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  25. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 2023-10-24 [Accession #: WE-23-0114399] was unsatisfactory: HPC 170 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on 2023-10-31 [Accession #: WE-23-0116822] was unsatisfactory (HPC: 7020 CFU/mL).
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  26. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 2023-10-24 [Accession #: WE-23-0114399] was unsatisfactory: HPC 170 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  27. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Filtration rate is too fast (17.35 gpm/sq.ft.). Maximum filtration rate is 15 gpm/sq.ft. Flow rate needs to be maintained between 59 gpm to 73 gpm. Make necessary adjustments.
  28. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result submitted on 2023-08-08 [Accession # WE: 23-0082333] was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Chemical parameters are not being documented as required.Requirement:Ensure all operating records, manual tests and automated controller readings are being documented as requested by EPH.
  29. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Chemical parameters are not being documented as required.Requirement:Ensure all operating records, manual tests and automated controller readings are being documented as requested by EPH.