MNP Community & Sport Centre - Competition Pool
2225 Macleod Trail SE Calgary AB T2G 5B6 · Aquatic Facility
10 inspections
- Demand Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The calculated turnover rate with operational flow rate of 1110 gpm was 9.3 hours. COMPLETE THE FOLLOWING:1. Ensure the turnover rate meets the requirements for pools built before November 2006:a. 6 hours, OR, 8 hours where it can be demonstrated that water quality can be maintained in accordance with the Pool Standards.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
0 infractions
- Demand Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- pH in automatic chemical feeder was set at 7.7.**Please ensure the pH is adjusted to 6.8 - 7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- pH in automatic chemical feeder was set at 7.7.**Please ensure the pH is adjusted to 6.8 - 7.6.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample collected on April 16, 2024 had an HPC count of 960 CFU/ml.Treat and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample for bacteriological analysis taken on 2024-02-27 was not processed as there was no identification on the bottle submitted. Please resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions