MNP Community & Sport Centre - Dive Tank
2225 Macleod Trail SE Calgary AB T2G 5B6 · Aquatic Facility
8 inspections
- Demand Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. Flow metres not installed. The Operator stated they are on order. In the meantime, they will have the flow rates measured by ultrasonic flow metre.COMPLETE THE FOLLOWING:1. Please install the flow metres and provide operational and maximum flow rates. 2. Update anti-entrapment plans.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH of the Diving tank was measured at 7.61, which can reduce the chlorine effectiveness. **Please ensure pH of the pool is maintained between 6.8 to 7.6 at all times.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- pH in automatic chemical feeder was set at 7.7.**Please ensure the pH is adjusted to 6.8 - 7.6.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH of the Diving tank was measured at 7.61, which can reduce the chlorine effectiveness. **Please ensure pH of the pool is maintained between 6.8 to 7.6 at all times.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- pH in automatic chemical feeder was set at 7.7.**Please ensure the pH is adjusted to 6.8 - 7.6.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The sample collected on April 30, 2024 has total coliforms present.Treat the pool and send in a resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample for bacteriological analysis taken on 2024-02-27 was not processed as there was no identification on the bottle submitted. Please resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions