MNP Community & Sport Centre - Teaching Pool

2225 Macleod Trail SE Calgary AB T2G 5B6 · Aquatic Facility

12 inspections

  1. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. A flow metre has not been installed.COMPLETE THE FOLLOWING:1. Install a flow metre.
  2. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. A flow metre has not been installed.COMPLETE THE FOLLOWING:1. Install a flow metre.
  3. Demand Inspection

    0 infractions

  4. Demand Inspection

    0 infractions

  5. Demand Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Combined chlorines measured 1.44 ppm. Ensure CCs are below 1 ppm.2. Alkalinity measured 48 ppm. Please ensure alkalinity is between 60-180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual reading is not consistent with the automatic reading. Please calibrate the pH probes and ensure manual readings are consistent with the automatic readings.
  6. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1. Combined chlorines measured 1.44 ppm. Ensure CCs are below 1 ppm.2. Alkalinity measured 48 ppm. Please ensure alkalinity is between 60-180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The manual reading is not consistent with the automatic reading. Please calibrate the pH probes and ensure manual readings are consistent with the automatic readings.
  7. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on May 14 2024, had HPC count of 1110 CFU/mL.REQUIREMENT: Review the water chemistry and treat the water. Take a re-sample once treatments are complete and the water chemistry is rebalanced.
  8. Demand Inspection

    0 infractions

  9. Risk Management Inspection

    0 infractions

  10. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample for bacteriological analysis taken on 2024-02-27 was not processed as there was no identification on the bottle submitted. Please resample.
  11. Monitoring Inspection

    0 infractions

  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The sample collected on April 25, 2023 had pseudomonas present. Spoke with aquatics manager Dave. Treat the basin, rebalance the chemistry, and send in a resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on September 23, 2023 was received more than 24 hours after collection.Resample.