Trailside Lodges - Swimming Pool
104 Armstrong Place Canmore AB · Aquatic Facility
16 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- No water sample was submitted the week of May 25/26. A water sample is required to be submitted each week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on June 5/26 was not tested as it was received at the lab after it had closed for the weekend. New water sample is to be submitted as soon as possible this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on February 12, 2026 was not tested as it leaked in transit. New sample to be submitted.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine was measured as 0.79ppm; was at 1.63ppm by end of the inspection.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- One of the skimmer weirs was missing. Was re-installed during inspection.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow meter does not read low enough to determine if minimum required flow rate is being met. Replace flow meter with one that reads lower.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Thursday September 25th, 2025 had an HPC of 340 CFU/ml.- Operators were informed to treat and re-sample.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- December 27, 2024 water sample was not tested. Resample to be submitted.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken Sept. 25/23 had total coliforms present. Treat water to remove contamination.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted this week was not tested as incorrect sampling date was written on the requisition form (Sept. 28th). Resample to be submitted.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- August 8/23 water sample had total coliforms present. Treat water to remove contamination.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- July 17/23 water sample had total coliforms isolated. Treat the water to remove contamination.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- July 17/23 water sample had total coliforms isolated. Treat the water to remove contamination.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- THE MINIMUM FLOW RATE THAT THE FLOW METER CAN READ IS 40GPM. THE MINIMUM REQUIRED FLOW RATE FOR THE POOL IS 14.5GPM AND THE MAXIMUM IS 37GPM SO ARE HAVING TO ESTIMATE THE FLOW. OBTAIN A FLOW METER THAT CAN READ A LOWER RANGE.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?