Trailside Lodges - Swimming Pool
104 Armstrong Place Canmore AB · Aquatic Facility
12 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- No water sample was submitted the week of May 25/26. A water sample is required to be submitted each week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on June 5/26 was not tested as it was received at the lab after it had closed for the weekend. New water sample is to be submitted as soon as possible this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on February 12, 2026 was not tested as it leaked in transit. New sample to be submitted.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free chlorine was measured as 0.79ppm; was at 1.63ppm by end of the inspection.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- One of the skimmer weirs was missing. Was re-installed during inspection.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Flow meter does not read low enough to determine if minimum required flow rate is being met. Replace flow meter with one that reads lower.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from Thursday September 25th, 2025 had an HPC of 340 CFU/ml.- Operators were informed to treat and re-sample.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- December 27, 2024 water sample was not tested. Resample to be submitted.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken Sept. 25/23 had total coliforms present. Treat water to remove contamination.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted this week was not tested as incorrect sampling date was written on the requisition form (Sept. 28th). Resample to be submitted.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Could not determine whether minimum flow rate is being met as the flow meter does not read low enough. Need to replace flow meter with one that has a lower range (can read down to 10gpm).
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Coud not locate anti-entrapment plan. Please provide a copy or re-write plan if can't be found.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?