Wingate By Wyndham Calgary Airport - Whirlpool

57 Freeport Crescent NE Calgary AB T3J 0T4 · Aquatic Facility

34 inspections

  1. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  2. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample (26ES-028E00275) collected on January 28th, 2026, came back unsatisfactory as the HPC was elevated (2960CFU/ml). Please resample the hot tub as soon as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  3. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  4. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on September 24, 2025, was unsatisfactory with an HPC of 290 CFU/mL.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  5. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  6. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Repeat violation:Water sample collected on 17/09/2025, had a HPC of 400 CFU/ml.Previous violation:ID 25ES253E00372The water sample collected on September 10, 2025, had a HPC count of 140 CFU/mL. - Submit a re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  7. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • ID 25ES253E00372The water sample collected on September 10, 2025, had a HPC count of 140 CFU/mL. - Submit a re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  8. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on July 30, 2025, had Pseudomonas Isolated in the sample.**Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on July 30, 2025, had a HPC count of 1200 CFU/mL. **Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  9. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on June 25, 2025, had Pseudomonas Isolated in the sample.**Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  10. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  11. Risk Management Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on May 7, 2025, had Pseudomonas Isolated in the sample.**Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on May 7, 2025, had a HPC count = 310 CFU/ml, which is higher than the required limit. **Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Disparity noted between the automatic chemical feeder reading (pH: 7.3) and manual testing (pH: 7.7). **Please calibrate the automatic feeder.**Compare readings from both automatic feeder and manual testing on regular basis for any inconsistencies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff are not documenting corrective action when pool chemical parameters are not in the required range.**Ensure records for all corrective actions taken are maintained.
  12. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on May 7, 2025, had Pseudomonas Isolated in the sample.**Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on May 7, 2025, had a HPC count = 310 CFU/ml, which is higher than the required limit. **Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine in the hot tub measured at 2.77 ppm.**Please keep combined chlorine levels as low as possible for optimal comfort of bathers.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  13. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine in the hot tub measured at 2.77 ppm.**Please keep combined chlorine levels as low as possible for optimal comfort of bathers.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  14. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on April 23, 2025, had Pseudomonas Isolated in the sample.**Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on April 23, 2025, had a HPC count > 57000 CFU/ml, which is significantly higher than the required limit. **Please begin treatment for the whirlpool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine in the hot tub measured at 2.77 ppm.**Please keep combined chlorine levels as low as possible for optimal comfort of bathers.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  15. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine in the hot tub measured at 2.77 ppm.**Please keep combined chlorine levels as low as possible for optimal comfort of bathers.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  16. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • **Corrected**FAC measured 0.33 ppm as the chemical feeder was turned off. - Operator turned on the chemical feeder and FAC measured 6 ppm during inspection. **Ensure FAC in the whirlpool (> 30*C) is maintained at 2 ppm or above at all times. **Ensure chemical feeder is turned on at all times. ***Ensure chlorine is not added manually in the whirlpool.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  17. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on March 26, 2025 had a HPC of 130 CFU.Please resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  18. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  19. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Due to error in sampling, no ID number was put on bottle and lab could not process. Resample must be processed immediately.
  20. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on January 15, 2025, had an HPC of 230 CFU/mL in the sample.REQUIREMENT: Begin treatment for the pool. Send a re-sample after you complete necessary treatments and when the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  21. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
  22. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1) The water sample collected on August 14, 2024, had Pseudomonas isolated in the sample.2) The water sample collected on August 20, 2024, had Pseudomonas isolated in the sample.REQUIREMENT: Begin treatment for the swimming pool immediately; Submit a re-sample after you complete necessary treatments and the water chemistry is rebalanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The water sample collected on August 14, 2024, had an HPC Count of >57000 CFU/mL.2) The water sample collected on August 20, 2024, had an HPC Count of 1480 CFU/mL.REQUIREMENT: Begin treatment for the swimming pool immediately; Submit a re-sample after you complete necessary treatments and the water chemistry is rebalanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
  23. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on August 14, 2024, had Pseudomonas isolated in the sample.REQUIREMENT: Begin treatment for the swimming pool immediately; Submit a re-sample after you complete necessary treatments and the water chemistry is rebalanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on August 14, 2024, had an HPC Count of >57000 CFU/mL.REQUIREMENT: Begin treatment for the swimming pool immediately; Submit a re-sample after you complete necessary treatments and the water chemistry is rebalanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
  24. Monitoring Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • **Ongoing violation** The flow rate of the swimming was 48 USGPM, which will achieve a turnover period of approximately 21 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **Ongoing Violation** There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers still appear properly secured and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. If this information cannot be located, promptly replace the covers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Ongoing Violation** The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  25. Risk Management Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the swimming was 45 USGPM, which will achieve a turnover period of 22 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **Ongoing Violation** There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers still appear properly secured and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. If this information cannot be located, promptly replace the covers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Ongoing Violation** The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  26. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on May 08, 2024, had total coliforms present in the sample.The water sample collected on May 15, 2024, had Pseudomonas isolated.REQUIREMENT: Close the whirlpool. Begin treatment for the pool. Collect and send a re-sample after you complete necessary treatments, and the water chemistry is balanced. Indicate on the requisition form that the sample is a ‘resample’.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the swimming was 45 USGPM, which will achieve a turnover period of 22 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **Ongoing Violation** There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers still appear properly secured and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. If this information cannot be located, promptly replace the covers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Ongoing Violation** The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  27. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on May 08, 2024, had total coliforms present in the sample.REQUIREMENT: Begin treatment for the pool. Collect and send a re-sample on Monday after you complete necessary treatments, and the water chemistry is balanced. Verify that correct sampling technique was conducted. Indicate on the requisition form that the sample is a ‘resample’.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the swimming was 45 USGPM, which will achieve a turnover period of 22 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **Ongoing Violation** There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers still appear properly secured and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. If this information cannot be located, promptly replace the covers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Ongoing Violation** The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  28. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The whirlpool water sample collected on February 21, 2024, showed that HPC was enumerated at 680 CFU/mL.-Please resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the swimming was 45 USGPM, which will achieve a turnover period of 22 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **Ongoing Violation** There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers still appear properly secured and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. If this information cannot be located, promptly replace the covers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Ongoing Violation** The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  29. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected around February 07, 2024, was not processed - the date and time of the collection was not provided on the requisition form.REQUIREMENT: Collect a new water sample and ensure the correct date is written on the requisition form.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the swimming was 45 USGPM, which will achieve a turnover period of 22 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **Ongoing Violation** There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers still appear properly secured and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. If this information cannot be located, promptly replace the covers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Ongoing Violation** The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  30. Demand Inspection

    6 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on January 24, 2024, has Pseudomonas isolated in the sample.REQUIREMENT: Refer to the Pseudomonas sheet (sent via email) and begin treatment for the whirlpool immediately. Send a re-sample for the whirlpool after you complete necessary treatments.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on January 24, 2024 had an HPC count of 680 CFU/mL.REQUIREMENT: Refer to the section regarding Pseudomonas treatment.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the swimming was 45 USGPM, which will achieve a turnover period of 22 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **Ongoing Violation** There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers still appear properly secured and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. If this information cannot be located, promptly replace the covers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Ongoing Violation** The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  31. Risk Management Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate of the swimming was 45 USGPM, which will achieve a turnover period of 22 minutes.REQUIREMENT: To achieve the required < 20 minutes turnover period, ensure the flow rate is above 52 USGPM
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • **Ongoing Concern** A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • **Ongoing Violation** There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers still appear properly secured and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. If this information cannot be located, promptly replace the covers.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Ongoing Violation** The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  32. Risk Management Inspection

    5 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The total alkalinity was tested with the inspector's kit and measured to be 59 ppm.REQUIREMENT: Maintain the total alkalinity between 60-180 ppm.2) The combined chlorine was tested on the inspector's kit and was measured to be 5.02 ppm. The operator recorded an earlier reading of 2.77 ppm.REQUIREMENT: Reduce the combined chlorines to the lowest level possible to maximize bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Last Inspection, it was noted that: "The filtration rate measured 16.3 USGPM/feet squared at the time of the inspection (flow rate measured 80 USGPM)."This inspection. the rates cannot be determined due to no flow meter installed on the system.REQUIREMENT: Install a flow meter on both swimming pool recirculation system. Ensure the flow is maintained to achieve the minimum turnover period but does not exceed the maximum rate of filtration.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1) There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers appeared properly secure and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. Provide this information to an Executive Officer by August 02, 2023. If any submerged suction outlet is expired, replace it immediately. 2) The combined chlorine test results, clarity of the water, time of water chemistry tests, and the pressure reading from the filter were not being recorded.REQUIRMENT: - Test and record the combined chlorine test results for the swimming pool daily.- Record the clarity of the swimming pool water daily.- Record the time of the swimming pool water chemistry tests daily.- Record the pressure readings from the swimming pool filters daily.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  33. Demand Inspection

    6 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on September 27, 2023, had pseudomonas detected in the sample.REQUIREMENT: Begin treatment for the whirlpool immediately and send a re-sample for the whirlpool after you complete necessary treatments.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The total alkalinity was tested with the inspector's kit and measured to be 59 ppm.REQUIREMENT: Maintain the total alkalinity between 60-180 ppm.2) The combined chlorine was tested on the inspector's kit and was measured to be 5.02 ppm. The operator recorded an earlier reading of 2.77 ppm.REQUIREMENT: Reduce the combined chlorines to the lowest level possible to maximize bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Last Inspection, it was noted that: "The filtration rate measured 16.3 USGPM/feet squared at the time of the inspection (flow rate measured 80 USGPM)."This inspection. the rates cannot be determined due to no flow meter installed on the system.REQUIREMENT: Install a flow meter on both swimming pool recirculation system. Ensure the flow is maintained to achieve the minimum turnover period but does not exceed the maximum rate of filtration.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1) There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers appeared properly secure and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. Provide this information to an Executive Officer by August 02, 2023. If any submerged suction outlet is expired, replace it immediately. 2) The combined chlorine test results, clarity of the water, time of water chemistry tests, and the pressure reading from the filter were not being recorded.REQUIRMENT: - Test and record the combined chlorine test results for the swimming pool daily.- Record the clarity of the swimming pool water daily.- Record the time of the swimming pool water chemistry tests daily.- Record the pressure readings from the swimming pool filters daily.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.
  34. Monitoring Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The operators of the pool have not taken a bacteriological water sample in over 3 years, despite the pool being operational at that time.REQUIREMENT: Take and submit a bacteriological water sample immediately, and ensure a bacteriological sample is submitted every week while the pool is operational.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1) The total alkalinity was tested with the inspector's kit and measured to be 59 ppm.REQUIREMENT: Maintain the total alkalinity between 60-180 ppm.2) The combined chlorine was tested on the inspector's kit and was measured to be 5.02 ppm. The operator recorded an earlier reading of 2.77 ppm.REQUIREMENT: Reduce the combined chlorines to the lowest level possible to maximize bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Last Inspection, it was noted that: "The filtration rate measured 16.3 USGPM/feet squared at the time of the inspection (flow rate measured 80 USGPM)."This inspection. the rates cannot be determined due to no flow meter installed on the system.REQUIREMENT: Install a flow meter on both swimming pool recirculation system. Ensure the flow is maintained to achieve the minimum turnover period but does not exceed the maximum rate of filtration.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • A certified pool operator was not operating and maintaining the pool on a day-to-day basis.REQUIREMENT: A certified pool operator must monitor the swimming pool basin daily. Ensure enough owners, owner’s agents, and/or staff members are certified by an organization that is on the List of Approved Pool Operator Education Organizations approved by the Minister.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1) There was no information to indicate when the submerged suction outlet covers were installed, and when they need to be replaced. Covers appeared properly secure and did not appear damaged.REQUIREMENT: Locate information detailing when the submerged suction outlet covers were installed, and when they need to be replaced. Provide this information to an Executive Officer by August 02, 2023. If any submerged suction outlet is expired, replace it immediately. 2) The combined chlorine test results, clarity of the water, time of water chemistry tests, and the pressure reading from the filter were not being recorded.REQUIRMENT: - Test and record the combined chlorine test results for the swimming pool daily.- Record the clarity of the swimming pool water daily.- Record the time of the swimming pool water chemistry tests daily.- Record the pressure readings from the swimming pool filters daily.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan was missing or not available on-site.REQUIREMENT: Reassess the swimming pool for all entrapment risks, and develop, implement, and maintain an anti-entrapment plan. Submit the plan to an Executive Officer with Environmental Public Health for review.