Comfort Inn & Suites by Calgary Airport North - Whirlpool
147 Freeport Crescent NE Calgary AB T3J 0T3 · Aquatic Facility
8 inspections
- Risk Management Inspection
1 infraction
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool. Operator pool certification expired in April 2024. Swimming pool must be maintained by a certified pool operator.**OUTSTANDING (2026-03-03). The pool operator was scheduled to take a pool operator course this March 24. Once the course is completed, please provide a copy of the certificate to the Executive Officer.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Demand Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH was measured below 6.5 (UR).
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The Free Available Chlorine was measured at 1.70 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Total Alkalinity was measured at 0 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The turnover period was measured at 22.8 minutes. The flow rate was measured at 47.5 GPM. Please increase the flow rate to be at least 54 GPM to achieve a turnover period of less than 20 minutes.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool. Operator pool certification expired in April 2024. Swimming pool must be maintained by a certified pool operator.**OUTSTANDING (2026-03-03). The pool operator was scheduled to take a pool operator course this March 24. Once the course is completed, please provide a copy of the certificate to the Executive Officer.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool. - Operator pool certification expired in April 2024. **Swimming pool must be maintained by a certified pool operator.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Risk Management Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Update July 2, 2025:pH measured less than 6.5 at the time of inspection. Update June 27, 2025:pH in the pool measured Under Range (i.e., below 6.5). - Operator raised the pH to 6.87. **Ensure pH is maintained between 6.8 and 7.6 at all times.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity measured 1 ppm at the time of inspection. **Ensure total alkalinity is maintained between 60 ppm and 180 ppm at all times.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated feeder display for pH was not consistent with manual tests; the display for pH was 7.4, whereas the inspector tested the pH below 6.5. **Please calibrate the probe.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool. - Operator pool certification expired in April 2024. **Swimming pool must be maintained by a certified pool operator.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH in the pool measured Under Range (i.e., below 6.5). - Operator raised the pH to 6.87. **Ensure pH is maintained between 6.8 and 7.6 at all times.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Outstanding**The flow rate is too slow and does not meet the minimum turnover for the whirlpool (< 20 minutes).When the operator increased the flow rate above 54 USGPM, the pump shut off for several instances.REQUIREMENT: Increase the flow rate to above 54 USGPM. If the pump is unable to maintain this flow rate, replace or repair the pump.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated feeder display for pH was not consistent with manual tests; the display for pH 7.2, whereas the inspector tested the pH at 6.87. **Please calibrate the probe.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- There is no person who is currently certified to operate the swimming pool. - Operator pool certification expired in April 2024. **Swimming pool must be maintained by a certified pool operator.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was tested and measured to be 54 ppm.REQUIREMENT: Maintain the total alkalinity between 60-180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate is too slow and does not meet the minimum turnover for the whirlpool (< 20 minutes).When the operator increased the flow rate above 54 USGPM, the pump shut off for several instances.REQUIREMENT: Increase the flow rate to above 54 USGPM. If the pump is unable to maintain this flow rate, replace or repair the pump.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on March 07, 2024, was not processed. The date/time of sample collection was later than the date of receipt.REQUIREMENT: Submit another water sample and ensure the paperwork is properly filled out.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was tested and measured to be 28 ppm.REQUIREMENT: Maintain the total alkalinity between 60-180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was tested and measured to be 28 ppm.REQUIREMENT: Maintain the total alkalinity between 60-180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?