Pomeroy Hotel & Conference Centre - Swimming Pool
11633 100 Street Grande Prairie AB T8V 3Y4 · Aquatic Facility
11 inspections
- Risk Management Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The pool has a single blockable submerged outlet and a secondary anti-entrapment device has not been employed. Update:A plan is in place to get an unblockable submerged outlet installed in the spring
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC count: 560 cfu/ml** Ensure water chemistry is within operating parameters and resample on the next sampling day.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The pool has a single blockable submerged outlet and a secondary anti-entrapment device has not been employed. Update:A plan is in place to get an unblockable submerged outlet installed in the spring
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The pool has a single blockable submerged outlet and a secondary anti-entrapment device has not been employed. ** Ensure to review secondary anti-entrapment options with a professional engineer. Options include:- Safety Vacuum Release System (SVRA)- Automatic pump shut off- Suction-limiting vent system- Permanently disable the single outlet. Verify that the overflow and skimmers are capable of handling the required system flow and that minimum turnover rates are achieved- A gravity flow system able to safely limit suction- Convert single suction outlet to return outlet by changing the piping, provided that the system piping and skimmer(s) are capable of handling the full system flowMain drain was turned off during visit and skimmers were capable of handling system flow and minimum turnover rate was not affected. Please ensure this secondary anti-entrapment method is verified by a professional engineer or if another method is better suited for the system
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample result was unsatisfactory, HPC = 1530cfu/ml- Increase Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.Run the water through the circulation system for at least one turnover. Balance water chemistry and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample result was unsatisfactory, HPC = 3660cfu/ml- Increase Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.Run the water through the circulation system for at least one turnover. Balance water chemistry and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Last bacteriological water sample was submitted on Dec 9.- ensure bacteriological water samples are submitted weekly.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample result was unsatisfactory, HPC =260cfu/ml Increase Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.Run the water through the circulation system for at least one turnover. Balance the water, resample as soon as posible.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Automated Controller reading;ORP- 696pH - 7.21PHI reading;pH - 7.2FAC- 0.84C.C - 0.28T.A - 115 Ensure FAC is maintained at a minimum of 1ppm or ORP at a minimum of 700.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?