Skip to content
Loading map…

Pomeroy Hotel & Conference Centre - Whirlpool

11633 100 Street Grande Prairie AB T8V 3Y4 · Aquatic Facility

10 inspections

  1. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on June 9, 2026.HPC: >57,000 CFU/mL.Ensure HPC is less than 100 CFU/mL.
  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on June 2, 2026.HPC: 280 CFU/mL.Ensure HPC is less than 100 CFU/mL.
  3. Demand Inspection

    0 infractions

  4. Monitoring Inspection

    0 infractions

  5. Risk Management Inspection

    0 infractions

  6. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample result was unsatisfactory indicating the presence of Pseudomonas aeruginosa.- Backwash and increase Free Available Chlorine (FAC) to 10 ppm and lower the pH to 6.8 - 7.0. Run the water through the circulation system for at least one turnover.Completely drain the whirlpool, scrub the whirlpool pool surfaces with acid or sanitizer, rinse off acid/sanitizer and refill the pool. Adjust water chemistry to regular operating parameters and submit a new water sample.
  7. Risk Management Inspection

    0 infractions

  8. Risk Management Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample result was unsatisfactory indicating the presence of Pseudomonas aeruginosa.- Backwash and increase Free Available Chlorine (FAC) to 10 ppm and lower the pH to 6.8 - 7.0. Run the water through the circulation system for at least one turnover.Completely drain the whirlpool, scrub the whirlpool pool surfaces with acid or sanitizer, rinse off acid/sanitizer and refill the pool. Adjust water chemistry to regular operating parameters and submit a new water sample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample result was unsatisfactory, HPC = 520cfu/ml- Increase Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.Run the water through the circulation system for at least one turnover. Balance water chrmistry water and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Last bacteriological water sample was submitted on Dec 6- ensure bacteriologicsl water samples are submitted weekly.
  9. Risk Management Inspection

    0 infractions

  10. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Hot tub volume is 3650 liters (3.65 cubic meters, 964.3G ).Flow rate - 55 GPMTurnover = 964.3/55= 17.5 minutesEnsure the turnover rate is maintained at 15 minutes or less.