Hampton Inn By Hilton Edmonton South - Whirlpool
10020 12 Avenue SW Edmonton AB T6X 0P6 · Aquatic Facility
16 inspections
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have not been installed during current inspection. Operations manager stated they can no longer get the direct replacement inlets but will have to speak with the supplier to determine what can be installed instead.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Previously noted leak was repaired however another leak was noted on the elbow just above the flow meter. Repair or replace the plumbing as required.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The skimmer pot lid on the SW corner of the tub was cracked and had a hole in it. Replace the lid as the sharp edges could be a injury hazard to patrons.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 10 April 2026 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 10 April 2026 was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have not been installed during current inspection. Operations manager stated they can no longer get the direct replacement inlets but will have to speak with the supplier to determine what can be installed instead.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Previously noted leak was repaired however another leak was noted on the elbow just above the flow meter. Repair or replace the plumbing as required.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The skimmer pot lid on the SW corner of the tub was cracked and had a hole in it. Replace the lid as the sharp edges could be a injury hazard to patrons.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have not been installed during current inspection. Operations manager stated they can no longer get the direct replacement inlets but will have to speak with the supplier to determine what can be installed instead.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Previously noted leak was repaired however another leak was noted on the elbow just above the flow meter. Repair or replace the plumbing as required.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The skimmer pot lid on the SW corner of the tub was cracked and had a hole in it. Replace the lid as the sharp edges could be a injury hazard to patrons.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have not been installed during current inspection
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The potable water fill line connected to the circulation pump was leaking while the operator was using it to prime the pump. Repair the leaking water fill line connection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have been purchased and are to be installed after grouting.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 15/08/2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 15/08/2025 was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have been purchased and are to be installed after grouting.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have been purchased and are to be installed after grouting.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have been purchased and are to be installed after grouting.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main drains in the whirlpool have expired. Facility is awaiting replacement parts from pool service provider. Whirlpool is closed to patrons until the main drains are replaced and compliant.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have been purchased and are to be installed after grouting.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rigid PVC schedule 80 pipes from the filter to the heater appeared to be warped and discolored. Facility management stated that they had a heater issue and are planning to replace them. The flow meter appeared to be damaged and was not returning to zero when the pump was turned off. Repair and replaced damaged piping.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Sections of the basin tile are missing and require repair. Repair damaged and missing tiles.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 2 Jan 2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on [Date] was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have been purchased and are to be installed after grouting.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rigid PVC schedule 80 pipes from the filter to the heater appeared to be warped and discolored. Facility management stated that they had a heater issue and are planning to replace them. The flow meter appeared to be damaged and was not returning to zero when the pump was turned off. Repair and replaced damaged piping.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Sections of the basin tile are missing and require repair. Repair damaged and missing tiles.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rigid PVC schedule 80 pipes from the filter to the heater appeared to be warped and discolored. Facility management stated that they had a heater issue and are planning to replace them. The flow meter appeared to be damaged and was not returning to zero when the pump was turned off. Repair and replaced damaged piping.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have been purchased and are to be installed after grouting.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Sections of the basin tile are missing and require repair. Repair damaged and missing tiles.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin. Inlets have been purchased and are to be installed after grouting.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 2024-02-16 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 2024-02-16 was unsatisfactory: HPC 390 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- A section of tiles are missing in the basin by the bottom of the stairs. Repair or replace this to prevent injury and/or further deterioration.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 27 Oct 2023 was unsatisfactory: HPC 1950 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- A section of tiles are missing in the basin by the bottom of the stairs. Repair or replace this to prevent injury and/or further deterioration.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The return inlets for the jets and the circulation system in the foot well were missing throughout the basin. Install proper eyeball fittings to ensure proper water circulation occurs in the basin.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- A section of tiles are missing in the basin by the bottom of the stairs. Repair or replace this to prevent injury and/or further deterioration.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The emergency pump shut off testing is not being consistently documented. Ensure that the tests are documented every two weeks. Suggest to create a separate document for testing.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?